E60
Built-in Potentiometer (Function selection)
E61
Terminal [12] Extended Function
E62
Terminal [C1] Extended Function
E60 through E62 define the property of the built-in potentiometer and terminals [12] and [C1],
respectively.
There is no need to set up the potentiometer and terminals if they are to be used for frequency
command sources.
Data for E60,
E61, or E62
Function
Description
0
None
--
1
Auxiliary frequency
command 1
This is an auxiliary analog frequency input to be added to
frequency command 1 (F01). It is never added to
frequency command 2, multistep frequency command or
other frequency commands.
2
Auxiliary frequency
command 2
This is an auxiliary analog frequency input to be added to
all frequency commands including frequency command
1, frequency command 2 and multistep frequency
commands.
3
PID command 1
This input includes temperature, pressure or other
commands to apply under the PID control.
Function code J02 should be also configured.
5
PID feedback amount
This input includes the feedback of the temperature or
pressure under the PID control. (Not available for E60.)
If the built-in potentiometer and different terminals have been set up to have the
same data, the operation priority is given in the following order:
E60 > E61 > E62
Selecting the
UP
/
DOWN
control (F01, C30 = 7) ignores auxiliary frequency
command 1 and 2.
C21
Timer Operation
C21 enables or disables a timer operation that is triggered by a run command and continues for
the timer count previously specified with the / keys. The operating procedure for the timer
operation is given below.
Data for C21
Function
0
Disable timer operation
1
Enable timer operation
• Pressing the
key during timer countdown quits the timer operation.
• Even if C21 = 1, setting the timer to 0 no longer starts the timer operation with the
key.
• Applying terminal command
FWD
or
REV
instead of the key command can also
start the timer operation.
5-56