(H codes continued)
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
H89
Electronic Thermal
Overload Protection for
Motor
(Data retention)
0: Disable
1: Enable
–
–
Y
Y
1
H91
PID Feedback W ire
Break Detection
(Terminal [C1])
0.0: Disable alarm detection
0.1 to 60.0: After the specified time, cause
alarm
0.1
s
Y
Y
0.0
H92
Continuity of
(P)
Running *1
(I)
0.000 to 10.000 times; 999
0.001
times
Y
Y1
Y2
999
H93
0.010 to 10.000 s; 999
0.001
s
Y
Y1
Y2
999
H94
Cumulative Run Time of
Motor 1
0 to 9999 (in units of 10 hours)
–
–
N
N
–
H95 DC Braking
(Braking response
mode)
0: Slow
1: Quick
–
–
Y
Y
0
H96
STOP Key Priority/Start
Check Function
Data STOP key priority Start check function
0: Disable
Disable
1: Enable
Disable
2: Disable
Enable
3: Enable
Enable
–
–
Y
Y
0
H97
Clear Alarm Data
0: Disable
1: Clear alarm data
–
–
Y
N
0
H98
Protection/Maintenance
Function
(Mode selection)
0 to 31 (decimal)
Bit 0: Lower the carrier frequency
automatically (0: Disable; 1: Enable)
Bit 1: Detect input phase loss
(0: Disable; 1: Enable)
Bit 2: Detect output phase loss
(0: Disable; 1: Enable)
–
–
Y
Y
3
5-14