![FujiFilm FVR-Micro Instruction Manual Download Page 39](http://html1.mh-extra.com/html/fujifilm/fvr-micro/fvr-micro_instruction-manual_2343270039.webp)
(F codes continued)
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
F18
Bias
(Frequency command 1)
-100.0 to 100.0 *1
0.01
%
Y*
Y
0.00
F20
DC Braking 1
(Braking starting
frequency)
(Braking level)
(Braking time)
0.0 to 60.0
0.1
Hz
Y
Y
0.0
F21
0 to 100 *2
1
%
Y
Y
0
F22
0.00 (Disable), 0.01 to 30.00
0.01
s
Y
Y
0.00
F23
Starting Frequency 1
(Holding time)
0.1 to 60.0
0.1
Hz
Y
Y
1.0
F24
0.00 to 10.00
0.01
s
Y
Y
0.00
F25
Stop Frequency
0.1 to 60.0
0.1
Hz
Y
Y
0.2
F26
Motor Sound
(Carrier frequency)
(Tone)
0.75 to 16
1
kHz
Y
Y
2
F27
0: Level 0 (Inactive)
1: Level 1
–
–
Y
Y
0
F30
Analog
Output
[FMA]
(Voltage adjustment)
(Function)
0 to 300
1
%
Y*
Y
100
F31
Select a function to be monitored from the
followings.
0: Output frequency 1 (before slip
compensation)
1: Output frequency 2 (after slip
compensation)
2: Output current
3: Output voltage
7: PID feedback amount (PV)
9: DC link bus voltage
14: Calibration
15: PID command (SV)
16: PID output (MV)
–
–
Y
Y
0
F37
Load Selection/Auto
Torque Boost
0: Variable torque load
1: Constant torque load
2: Auto-torque boost
–
–
N
Y
1
F39
Stop Frequency
(Holding Time)
0.00 to 10.00
0.01
s
Y
Y
0.00
F42
Control Mode Selection
1
0: V/f control with slip compensation
inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
–
–
N
Y
0
5-4