(F codes continued)
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
F43
Current Limiter
(Mode selection)
(Level)
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable
during ACC/DEC)
2: Enable during ACC/constant speed
operation
–
–
Y
Y
2
F44
20 to 180 : 3.7 kW(5HP)
(The data is interpreted as the rated
output current of the inverter for
100%.) *2
1
%
Y
Y
160
F50
Electronic Thermal
Overload Protection for
Braking Resistor
(Discharging capability)
(Allowable average loss)
1 to 900, OFF (Cancel)
1
kWs
Y
Y1
Y2
OFF
F51
0.001 to 50.00
0.001 kW
Y
Y1
Y2
0.001
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED
monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 The percentage is relative to the rated output current.
5-5