Type (FRN
E1S-2U)
Applicable motor rating [HP] (*1)
F12
1/8
0.3
0.8
1.3(0.6)
2.4(1.1)
2.6(1.2)
3.7(1.7)
3.7(1.7)
5.1(2.3)
7.5(3.4)
7.9(3.6)
13(6.1)
16(7.1)
1.3(0.6)
1.5(0.7)
1.8(0.8)
3.7(1.7) 3.7(1.7)
5.1(2.3)
7.5(3.4) 7.9(3.6)
13(6.1)
16(7.1)
F25
1/4
0.6
1.5
F50
1/2
1.2
3.0
002
2
3.2
8.0
001
1
2.0
5.0
003
3
4.4
11
005
5
6.8
17
007
7.5
10
25
010
10
13
33
020
20
24
60
015
15
19
47
Applicable safety standards
Enclosure (IEC60529)
Cooling method
Weight / Mass [lbs(kg)]
Rated capacity [kVA] (*2)
Rated voltage [V] (*3)
Rated current [A] (*4)
Overload capability
Rated frequency [Hz]
Phases, voltage, frequency
Voltage/frequency variations
Rated current [A] (*9)
(with
DCR)
(without
DCR)
Required power supply capacity [kVA] (*5)
Torque [%] (*6)
Torque [%] (*7)
DC injection braking
Braking transistor
Item
Specifications
Type (FRN
E1S-4U)
Applicable motor rating [HP] (*1)
F50
1/2
1.2
001
1
2.0
002
2
2.9
003
3
4.4
005
5
7.2
007
7.5
10
010
10
14
015
15
19
020
20
24
0.85
1.7
0.6
1.6
3.1
1.1
3.0
5.9
2.0
4.4
8.2
2.9
7.3
13.0
4.9
10.6
17.3
7.4
14.4
23.2
10
21.1
33.0
15
28.8
43.8
20
1.5
2.5
3.7
5.5
13
18
24
30
20
40
70
100
9.0
Applicable safety standards
Enclosure (IEC60529)
Cooling method
Weight / Mass [lbs(kg)]
Rated capacity [kVA] (*2)
Rated voltage [V] (*3)
Rated current [A] (*4)
Overload capability
Rated frequency [Hz]
Phases, voltage, frequency
Voltage/frequency variations
Rated current [A] (*9)
(with
DCR)
(without
DCR)
Required power supply capacity [kVA] (*5)
Torque [%] (*6)
Torque [%] (*7)
DC injection braking
Braking transistor
Item
Specifications
(1.4)
(0.7)
0.57
1.1
0.2
0.93
1.8
0.3
1.6
3.1
0.6
3.0
5.3
1.1
5.7
9.5
2.0
8.3
13.2
2.9
14.0
22.2
4.9
21.1
31.5
7.4
28.8
42.7
10
42.2
60.7
15
57.6
80
20
(4.2)
150
100
70
20
40
(2.5)
(10)
(7.0)
(23.5)
(16.5)
(31)
(57)
(44)
150% of rated current for 1min, 200% - 0.5s
50, 60Hz
Three-phase, 200 to 240V, 50/60Hz
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5%
Three-phase, 380 to 480V, 50/60Hz
Voltage: +10 to -15% (Voltage unbalance (*8): 2% or less) Frequency: +5 to -5%
Built-in
UL508C, C22.2No.14, EN50178:1997
IP20, UL open type
Natural cooling
Fan cooling
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 100% of rated current
150
-
UL508C, C22.2No.14, EN50178:1997
IP20, UL open type
Natural cooling
Fan cooling
Starting frequency: 0.1 to 60.0Hz, Braking time: 0.0 to 30.0s, Braking level: 0 to 100% of rated current
150
Built-in
■
Three-phase 230V (1/8 to 20HP)
■
Three-phase 460V (1/2 to 20HP)
●
Standard type
(*1) Fuji's 4-pole standard motor
(*2) Rated capacity is calculated by assuming the output rated voltage as 230V for three-phase 230V series and 460V for three-phase 460V series.
(*3) Output voltage cannot exceed the power supply voltage.
(*4) When setting the carrier frequency (F26) to 3 kHz or less. Use the current ( ) or below when the carrier frequency setting is higher than 4kHz and continuously operating at 100%.
(*5) Obtained when a DC REACTOR is used.
(*6) Average braking torque obtained when reducing the speed from 60Hz with AVR control OFF (Varies with the efficiency of the motor.)
(*7) Average braking torque obtained by use of external braking resistor (standard type available as option)
(*8) Voltage unbalance [%] =
Max voltage [V] - Min voltage [V]
x 67 (IEC 61800-3)
Three-phase average voltage [V]
If this value is 2 to 3%, use AC REACTOR (ACR: option).
(*9) The value is calculated on assumption that the inverter is connected with a power supply capacity of 500kVA (or 10 times the inverter capacity if the inverter capacity exceeds 50kVA) and %X is 5%.
Three-phase 380V to 480V (with AVR function)
150% of rated current for 1min, 200% - 0.5s
50, 60Hz
Three-phase 200V to 240V (with AVR function)
Output ratings
Input power
Braking
Output ratings
Input power
Braking
-
Type (FRN
E1S-7U)
Applicable motor rating [HP] (*1)
F12
1/8
0.3
1.3(0.6)
1.3(0.6)
1.5(0.7)
2.0(0.9)
4.0(1.8)
5.3(2.4)
1.1
1.8
0.3
2.0
3.3
0.4
3.5
5.4
0.7
6.4
9.7
1.3
11.6
16.4
2.4
17.5
24.8
3.5
0.8
(0.7)
(1.4)
(2.5)
(4.2)
(7.0)
(10)
1.5
150
100
Built-in
Fan cooling
70
40
8.0
11
3.0
5.0
F25
1/4
0.6
F50
1/2
1.2
001
1
2.0
002
2
3.2
003
3
4.4
Applicable safety standards
Enclosure (IEC60529)
Cooling method
Weight / Mass [lbs(kg)]
Rated capacity [kVA] (*2)
Rated voltage [V] (*3)
Rated current [A] (*4)
Overload capability
Rated frequency [Hz]
Phases, voltage, frequency
Voltage/frequency variations
Rated current [A] (*9)
(with
DCR)
(without
DCR)
Required power supply capacity [kVA] (*5)
Torque [%] (*6)
Torque [%] (*7)
DC injection braking
Braking transistor
Item
Specifications
■
Single-phase 230V (1/8 to 3HP)
150% of rated current for 1min, 200% - 0.5s
50, 60Hz
Single-phase, 200 to 240V, 50/60Hz
Voltage: +10 to -10%, Frequency: +5 to -5%
UL508C, C22.2No.14, EN50178:1997
IP20, UL open type
Natural cooling
Starting frequency: 0.1 to 60.0Hz, Braking level: 0 to 100% of rated current, Braking time: 0.0 to 30.0s
150
Three-phase 200V to 240V (with AVR function)
Output ratings
Input power
Braking
Specifications