Terminal Functions
Symbol
Terminal name
Functions
Remark
Related
function
code
(FMA)
(FMP)
Connectable impedance (Minimum impedance:
7.5HP(5kW) In the (0 to +10V DC)
In case of voltage output, up to two analog
voltmeters (0 to 10V DC, input impedance:
10kW) can be connected.Gain adjustment
range: 0 to 300%
Up to two analog voltmeters
(0 to10V DC, input impedance:
10k
Ω
) can be connected.
(Driven at average voltage)
Max. voltage: 27V DC
Max. current: 50mA
Leak current: 0.1mA max.
ON voltage: within 2V (at 50mA)
•
Short circuit across terminals CM and CMY to use.
•
Same terminal as digital input PLC terminal
Detection width: 0 to 10.0 [Hz]
Operation level: 0.0 to 400.0 [Hz]
Hysteresis width: 0.0 to 400.0 [Hz]
The terminal is isolated from terminals 11 and CM.
Contact capacity: 250V AC,0.3A,
cos
φ
=0.3, +48V DC, 0.5A
Power (+5V) is supplied to the
keypad.
A monitor signal of analog DC voltage between 0 to +10V DC) can be output
for the item selected from the following:
•
Output frequency 1 (before slip compensation)
•
Output frequency 2 (after slip
compensation)
•
Output current
•
Output voltage
•
Output torque
•
Load factor.
•
Power consumption
•
PID feedback value (PV)
•
DC link circuit voltage
•
Universal
AO.
•
Motor output
•
Analog output test.
•
PID command (SV)
•
PID output (MV)
One of the following items can be output in a pulse frequency.
•
Output frequency 1 (before slip compensation)
•
Output frequency 2 (after slip
compensation)
•
Output current
•
Output voltage
•
Output torque
•
Load factor.o
Power consumption
•
PID feedback value (PV)
•
DC link circuit voltage
•
Universal
AO
•
Motor output
•
Analog output test
•
PID command (SV)
•
PID output (MV)
The following functions can be set at terminals Y1 or Y2 for signal output.
•
The setting of "short circuit upon active signal output" or "open upon active
signal output" is possible.
•
Sink/source support (switching unnecessary)
An ON signal is output at output frequencies above a preset detection level.
The signal is deactivated if the output frequency falls below the detection level.
The OFF signal is output when the inverter is running in drive mode and the
ON signal is output in the braking mode or stopped state.
If more than 20ms elapse while one of the following operations is operating:
current limiter for the inverter, automatic deceleration operation or torque limiter.
•
A no-voltage contact signal (1c) is issued when the inverter is stopped due to an alarm.
•
Multi-purpose relay output; signals similar to above-mentioned signals Y1 to Y2 can be selected.
•
An alarm output is issued upon either excitation or no excitation according to selection.
One of the following protocols can be selected.
•
Protocol exclusively for keypad (default selection)
•
Modbus RTU
•
Fuji's special inverter protocol
•
SX protocol for PC loader
Analog monitor
Pulse monitor
Transistor output
power
Transistor output 1
Transistor output 2
Inverter running
Inverter output on
Speed/freq. arrival
Speed/freq. detection
Undervoltage detection
Torque polarity
detection
Inverter output limit (limit on current)
Auto-restarting
Overload early warning (motor)
Operation ready output
Motor 2 switching
Retry in action
Heat sink overheat early warning
Frequency arrival 2
Inverter output limit
Lifetime alarm
Command loss detection
Overload preventive control
Current detection
Current detection 2
PID alarm output
Brake signal
Alarm relay output (for any fault)
Transistor output common
Alarm relay output
(for any fault)
RJ-45 connector for
connection of keypad
Power supply for a transistor output load. (24V DC 50mA DC Max)
An ON signal is output when the inverter runs at higher than the starting frequency.
A signal is issued when the inverter runs at smaller than the starting frequency or when DC braking is in action.
An active signal is issued when the output frequency reaches the set frequency.
The signal is output when the inverter stops because of undervoltage.
The signal is output when the inverter is limiting the current.
The signal is output during auto restart operation (after momentary power failure and until completion of restart).
The signal is output when the electronic thermal relay value is higher than the preset alarm level.
A signal is issued if preparation for inverter operation is completed.
The motor switching signal (M2/M1) is input and the ON signal is output when the motor 2 is selected.
The signal is output during an active retry.
An early warning signal is issued before the heat sink trips due to overheat.
The signal is output when the time set in E29 elapses after the frequency arrival signal (FAR) is output.
Outputs alarm signal according to the preset lifetime level.
A loss of the frequency command is detected.
The signal is output when the overload control is activated.
The signal is output when a current larger than the set value has been detected for the timer-set time.
The signal is output when a current larger than the set value 2 has been detected for the timer-set time.
An absolute value alarm or deviation alarm under PID control is issued as a signal.
The signal for enabling or releasing the brake is output.
An alarm relay output (for any fault) signal is issued as a transistor output signal.
Common terminal for transistor output
F29 to
F31
F29,
F31,
F33
E20
E21
E22
E30
E31
E32
F43, F44
F14
F10 to F12
H04, H05
E29
F41 to F44
H69
H42, H43, H98
E65
H70
E34, E35
E37, E38
J11 to J13
J68 to J72
E27
FM
(PLC)
Y1
Y2
CMY
30A,30B,30C
-
(RUN)
(RUN2)
(FAR)
(FDT)
(LV)
(B/D)
(IOL)
(IPF)
(OL)
(RDY)
(SWM2)
(TRY)
(OH)
(FAR2)
(IOL2)
(LIFE)
(REF OFF)
(OLP)
(ID)
(ID2)
(PID-ALM)
(BRKS)
(ALM)
H30
y01 to y20
y98,y99
Division
Analog output
Pulse output
T
ransistor output
Contact output
Communication
Terminal
Functions