![Fuji Electric ZSVS-2 Instruction Manual Download Page 60](http://html1.mh-extra.com/html/fuji-electric/zsvs-2/zsvs-2_instruction-manual_2341922060.webp)
- 48 -
INZ-TN2ZSVS-E
4.3.3 Selecting output
Current output (4 to 20mA DC) or voltage output (0 to 1V DC) can be selected in this mode.
To switch between current and voltage outputs, switch the jumper pin of the control printed board.
“Depends on specifications.”
Initial value
Select “4 to 20mA DC” or “0 to 1V DC.”
Setting contents
Output cannel
Jumper
4 to 20mA DC
0 to 1V DC
CH1
JP1
1-2
2-3
CH2
JP2
1-2
2-3
CH3
JP3
1-2
2-3
CH4
JP4
1-2
2-3
CH5
JP5
1-2
2-3
CH6
JP6
1-2
2-3
CH7
JP7
1-2
2-3
CH8
JP8
1-2
2-3
Jumper switching
• When making the setting in this mode, be sure to switch the jumper pin of the control printed
board. Otherwise accurate output signal cannot be obtained.
Caution on setting
1 JP8 3
(4 to 20mA DC)
Between 1 and 2
(0 to 1V DC)
Between 2 and 3
1 JP8 3
JP1 JP2 JP3 JP4 JP5 JP6 JP7
JP8