1-19
Section 1 Specifications
Address
Name
Description
%MX10.49.0
Main unit running
ON while the main unit is running.
%MX10.49.1
|
%MX10.49.15
Not used
Address
Name
Description
%MX10.50.0
Main unit configuration
ON while the main unit is running normally or in a nonfatal fault condition.
%MX10.50.1
|
%MX10.50.15
Not used
%MX10.51.0
Main unit error
ON while the main unit is stopped due to a fatal fault or running in a nonfatal
fault condition.
%MX10.51.1
|
%MX10.51.15
Not used
Resource configuration
information
Resource fault
information
Resource status
OFF
OFF
Nonexistent
ON
OFF
Normal (running or stopped)
ON
ON
Nonfatal fault (running or stopped)
OFF
ON
Fatal fault
(14)
Resource running information
%MW10.49 (Read only)
(15) Resource configuration/fault information %MW10.50, %MW10.51 (Read only)
The resource configuration/fault information enables an application program to recognize the status of the main unit.