3.3.8 Peripheral devices
・
RHC132S to450S-69DE Filter stack application table
MD mode
RHC-D type
RHF-D
type
Rated current
of MCCB
and ELCB(A)
Magnetic
contactor (52)
Fuse (Fac)
Microswitch
Type
Qty.
Type
Qty.
Type
Qty.
RHC132S-69DE
RHF160S-69DE
175
SC-N6
1
170M5447
3
170H3027
3
RHC160S-69DE
RHF160S-69DE
200
SC-N7
1
RHC200S-69DE
RHF220S-69DE
250
SC-N8
1
170M5448
3
RHC250S-69DE
RHF280S-69DE
300
SC-N8
1
170M6548
3
RHC280S-69DE
RHF280S-69DE
350
SC-N11
1
RHC315S-69DE
RHF355S-69DE
400
SC-N11
1
RHC355S-69DE
RHF355S-69DE
500
SC-N12
1
170M6500
3
RHC400S-69DE
RHF450S-69DE
500
SC-N12
1
RHC450S-69DE
RHF450S-69DE
600
SC-N14
1
LD mode
RHC-D type
RHF-D
type
Rated current
of MCCB
and ELCB(A)
Magnetic
contactor (52)
Fuse (Fac)
Microswitch
Type
Qty.
Type
Qty.
Type
Qty.
RHC132S-69DE
RHF160S-69DE
200
SC-N7
1
170M5447
3
170H3027
3
RHC160S-69DE
RHF220S-69DE
250
SC-N8
1
RHC200S-69DE
RHF220S-69DE
300
SC-N8
1
170M5448
3
RHC250S-69DE
RHF280S-69DE
350
SC-N11
1
170M6548
3
RHC280S-69DE
RHF355S-69DE
400
SC-N11
1
RHC315S-69DE
RHF355S-69DE
500
SC-N12
1
RHC355S-69DE
RHF450S-69DE
500
SC-N12
1
170M6500
3
RHC400S-69DE
RHF450S-69DE
600
SC-N14
1
The above table lists the rated current of MCCBs and RCD/ELCBs to be used in the power control
panel with an internal temperature of lower than 50
°
C. The rated current is factored by a correction
coefficient of 0.85 as the RCDs'/MCCBs' and ELCBs' original rated current is specified when using
them in a surrounding temperature of 40
°
C or lower. Select an MCCB and/or RCD/ELCB suitable for
the actual short-circuit breaking capacity needed for your power systems.
3-24