Table 11.2-2 Fundamental Functions (F codes)
Function
code
Communications
address
Function code name
Data setting range
Format
485 No Link No.
F00
0h
46h
Data protection
0 or 1
0: Enable data change
1: Protect data
This write-protects data from the keypad.
Use "
STOP
+
Λ
/ V" keys to change data.
40
F01
1h
47h
Harmonics suppressing
filter
0 or 1
0: With filter
1: Without filter
41
F02
2h
48h
Restart mode after
momentary power failure
(Selection)
0 or 1
0: Disable
1: Enable
42
F03
3h
49h
Current rating switching
0 or 1
0: MD mode (Overload current 150%)
1: LD mode (Overload current 110%)
43
F04
4h
4Ah
LED monitor
(Display selection)
0 to 5
0: Input power 1 (%)
1: Input power 2 (kW)
2: Input current (rms) (A)
3: Input voltage (rms) (V)
4: DC link bus voltage (V)
5: Source frequency (Hz)
44
F05
5h
4Bh
LCD monitor
(Display selection)
0 to 2
Switches the Run mode screen on the keypad.
0: Operation guide screen
1: Bar graph of running data 1 (Input power and
input current (rms))
2: Bar graph of running data 2 (Source voltage
fluctuation and source frequency fluctuation)
45
F06
6h
4Ch
LCD monitor
(Language selection)
0 to 2
0: Japanese
1: English
2: Chinese
46
F07
7h
4Dh
LCD monitor
(Contrast adjustment)
0 to 10
0 (Low) to 10 (High)
0
F08
8h
85h
Carrier frequency
Fixed at 5 kHz even any setting is made.
(2.5 kHz when the OPC-VG7-SIR is mounted)
59