55
EN-US
Technical Data
Fronius Symo
10.0-3 208-240
12.0-3 208-240
Input Data
MPP voltage range
300–500 V DC
Input voltage range (at 1000 W/m² / 14°F in an open circuit)
200–600 V DC
Max. input current (MPP1/MPP2)
(MPP1 + MPP2)
25.0/16.5 A
41.5 A
Max. short circuit current of solar modules (I
SC PV
) (MPP1/MPP2)
37.5/24.8 A
Max. recovery current
4)
37.5/24.8 A (RMS)
5)
Output Data
Nominal output power (P
nom
)
9995 W
11995 W
Max. output power (+104°F)
9995 W
11995 W
Max. output power (+122°F)
at 208 V
9800 W
9800 W
at 220 V
9995 W
11300 W
at 240 V
9995 W
11300 W
Phases
3 ~ NPE
Nominal grid voltage
at 208 V
120/208 V
at 220 V
127/220 V
at 240 V
120/240 V
Operating range AC voltage
-12 +10%
Grid voltage setting range
60–152 V; 104–288 V
Nominal output current
at 208 V
27.8 A
33.3 A
at 220 V
26.2 A
31.5 A
at 240 V
24.1 A
28.9 A
Maximum output current
at 208 V
31.5 A
35.0 A
at 220 V
29.8 A
35.0 A
at 240 V
27.4 A
32.8 A
Max. output residual current per duration
64 A/2.34 ms
Nominal frequency
50/60 Hz
1)
Total harmonic distortion
< 1.5%
< 1.75%
Power factor (cos phi)
0 - 1 ind./cap.
2)
General Data
Maximum efficiency
97.00%
CEC efficiency
at 208 V
96.50%
96.50%
at 220 V
at 240 V
96.50%
96.50%
Cooling
Controlled forced-air ventilation
Protection class
NEMA 4X
Dimensions h x w x d
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
Weight (full/lite version)
91.9 / 91.3 lbs. (41.7 / 41.3 kg)
Permissible ambient temperature
-40°F to +140°F (-40°C to +60°C)