48
*) If status code persists: Contact a Fronius-trained service technician
**) Fault is corrected automatically. If this status code keeps recurring, contact your system
installer
Class 4 Status
Codes
Class 4 status codes may require the intervention of a trained Fronius service technician.
305
No feed-in despite closed relay
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
**)
306
There is insufficient PV power for grid
power feed operation
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
Wait for sufficient solar
radiation;
**)
307
DC low
DC input voltage is too low for grid
power feed operation
IMPORTANT!
Status codes 306 (Power low) and 307 (DC low) appear naturally every morning and evening due
to low solar irradiance. These status codes are not the result of a fault.
308
Intermediate circuit voltage too high
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
**)
309
DC input voltage MPPT1 too high
311
DC strings polarity reversed
313
DC input voltage MPPT2 too high
314
Timeout current sensor calibration
Short interruption of grid power
feed operation.
The inverter returns to the
startup phase.
*)
315
AC current sensor fault
316
InterruptCheck fail
325
Overtemperature in connection area
326
Fan 1 error
327
Fan 2 error
Code
Description
Behavior
Remedy
Code
Description
Behavior
Remedy
401
Communication with power module is
not possible
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
*)
406
AC module temperature sensor faulty
(L1)
407
AC module temperature sensor faulty
(L2)
408
Direct component measured in the sup-
ply grid too high
412
The "fixed voltage" setting has been se-
lected instead of MPP voltage operation
and the voltage is set to a value that is
too low or too high.
-
**)
415
Safety cut-out triggered by option card or
RECERBO
Inverter does not feed ener-
gy into the grid.
*)
416
No communication between power mod-
ule and control unit
The inverter will automati-
cally attempt to connect
again and, if possible, re-
sume feeding energy into
the grid
*)