Inserting String Fuses
Selecting
String Fuses
Only use fuses for solar modules that meet the proper requirements for
string fuses from the solar module manufacturer or as per the „Criteria for
the Proper Selection of String Fuses“ section:
-
max. 20 A per fuse holder
-
max. 25 solar module strings
-
max. 50 A per measuring channel
-
max. 250 A of total input current
-
Fuse dimensions: Diameter 10 x 38 mm
Important
-
Please follow solar module safety instructions
-
Follow all solar module manufacturer requirements
Inserting
String Fuses
NOTE
Insert string fuses in the fuse holders corresponding to the
number of available solar modules.
WARNING!
An electrical shock can be fatal. Danger from DC
voltage from solar modules.
-
Make sure that the input and output sides in front of the
device are not charged before conducting any connection
or maintenance work.
-
Never remove or insert a fuse while it is under load.
-
Any and all connections should only be carried out by quali-
fied electricians.
-
Follow the safety rules in these operating instructions.
Safety
Summary of Contents for String Control 250/ 25 DCD DF
Page 2: ......
Page 4: ......
Page 50: ...40...
Page 54: ......
Page 98: ...40...
Page 102: ......
Page 149: ...ud_fr_st_et_01482 012007 ZH...
Page 150: ......
Page 151: ...ud_fr_se_sv_01483 012012 I ZH...
Page 152: ...ud_fr_se_sv_01483 012012 II...
Page 153: ...ud_fr_se_sv_01483 012012 III ZH...
Page 154: ...ud_fr_se_sv_01483 012012 IV...
Page 155: ...1 ZH...
Page 156: ...2...
Page 157: ...3 ZH...
Page 158: ...4...
Page 159: ...5 ZH...
Page 160: ...6...
Page 161: ...7 ZH 1 2 3 4 5 6 7 8 9 10 11 12 19 13 17 14 15 16 18 20 21 22 23 24 25 26 27 28 29 1XX 0XX...
Page 162: ...8...
Page 163: ...9 ZH...
Page 164: ...10...
Page 165: ...11 ZH 3 2 3 4 4 x 1 4 1 2 3 x 4 5 3 2 1 2 4 3 1 2 1 1 3 5 4...
Page 167: ...13 ZH 1 1 2 3...
Page 168: ...14...
Page 170: ...16 3 10mm 1 2 5 3 4 A B 2 5 10mm 1 2 4 3 A B 1 3 1 1 2 3 4...
Page 171: ...17 ZH 4 3 2 4 5 6 1 3 3 2 4 5 6 1 2 1 2 1 2 1 1 2 M12 M12 3 4 M12 M12...
Page 172: ...18...
Page 173: ...19 ZH...
Page 174: ...20...
Page 175: ...21 ZH 2 1 1 1 2 1 2 1 Strang...
Page 176: ...22...
Page 177: ...23 ZH Line ISDN OUT IN OUT IN OUT IN...
Page 178: ...24 4 2 1 3 3 1 3 DATCO M IN DATCO M O UT 2 2 IN OUT 1 2 1 3 1 2...
Page 179: ...25 ZH 3 10mm 1 2 2 1...
Page 180: ...26 5 1 4 4 3 6 5 OUT IN 2 1 IN OUT 12 V GND TX RX RX TX GND 12 V 12 V GND RX TX TX RX GND 12 V...
Page 181: ...27 ZH 1 2...
Page 182: ...28 1 2...
Page 183: ...29 ZH...
Page 184: ...30...
Page 185: ...31 ZH 6 1 5 1...
Page 186: ...32 1XX 0XX 0XX 1XX 0XX 1XX 0XX 1XX 0 1 0 3 7 0 2 3 1 2 3 1...
Page 187: ...33 ZH 1 4 3 3 4 2 1 1 OFF ON 1 1 1 1...
Page 188: ...34 1 2 3...
Page 189: ...35 ZH...
Page 190: ...36...
Page 191: ...37 ZH 1...
Page 192: ...38...
Page 193: ...39 ZH 1 1 1 2 2 2 1 2 1 2...
Page 194: ...40...