Operating the System
Froling GmbH, Industriestraße 12, 4710 Grieskirchen, AUSTRIA
Page 29
www.froling.com
B0600008_US
3
Light up the newspaper
Turn on the Induced Draft Fan again by pressing UP arrow key
Keep Ignition Door ajar.
Step aside from boiler doors and watch boiler until flue gas tempera-
ture displayed exceeds 130°C (270°F).
Never leave boiler unattended before Ignition procedure is success-
fully finished
In case of strong smell of smolder or fume coming out of the Ignition
Door close Ignition Door and Insulation Door immediately and follow
Caution instructions “Explosive Gases!” at Caution Labels
In case flue gas temperature does not exceed 130°C (270°F)
within 15 minutes:
Close both Ignition Door and Insulation Door
In case any error message is displayed at Boiler Control System
or display is blank:
Refer to chapter 6 “Troubleshooting”
If necessary cautiously repeat Ignition procedure
Close Ignition Door
Close Insulation Door
Boiler Control shall be in “Heating”
or "Heating up" mode