Boiler Control System Lambdatronic S 3200
Froling GmbH, Industriestrasse 12, A-4710 Grieskirchen, Austria
Page 51
www.froling.com
M1060008_US
5
5.2
Initial start-up (programming the controller)
After power up the start logo is displayed. The
Boiler Control System performs a system check.
After the system check the Basic Display is
shown. The Basic Display is shown as default
during normal operation, giving information
about the two most important parameters; the
display can be configured individually.
5.2.1
Changing the User Level
For safety reasons certain parameters are only visible at specific
User Levels. To change to another level it is necessary to enter
the relevant user code:
...
Child lock
(User Code 0)
At “Child lock” level, only the Basic Display is shown.
It is not possible to change any parameter at this level.
Owner
(User Code 1)
Standard level for normal operation of controls. All parameters for Owner’s
use are displayed and released for adjustment.
Installer / Service*
Detailed level for Installation and Service purposes. All parameters and
system controls available are displayed and released for adjustment. All
parameters shown in these operating instructions are available.
*Installer: Please call Tarm Biomass for Installer Code.
repeatedly
repeatedly