5.4.5 Chamber discharge system
Sliding floor
System menu
Fuel feed
Chamber discharge system
Sliding floor
Sliding floor startup delay
If the light barrier of the filling level monitor to the transfer
position is unoccupied for longer than the set value, the
sliding floor is switched on.
Sliding floor shutdown delay
If the light barrier of the filling level monitor to the transfer
position is occupied with material, the sliding floor is
switched off with a delay by this set value.
Discharge runtime until sliding floor automatic run
If the discharge runs for the set amount of time without the
light barrier indicating that the sliding floor is empty, then
the automatic run of the sliding floor is activated. This
causes any jammed material in the area of the light barrier
of the sliding floor to loosen again.
Sliding floor automatic run runtime
Specifies the duration of the automatic run.
Maximum runtime discharge when overfilling sliding floor
The sliding floor is stopped immediately if the overflow
sensor in the sliding floor is triggered. The boiler continues
to operate to reduce the overfilling. If the discharge is
active for the time set for this parameter and the overfilling
is still present, the boiler will shut down.
Sliding floor container
System menu
Fuel feed
Chamber discharge system
Sliding floor container
Sliding floor active
Queries whether a sliding floor is present.
Sliding floor startup delay
If the light barrier of the filling level monitor to the transfer
position is unoccupied for longer than the set value, the
sliding floor is switched on.
Sliding floor shutdown delay
If the light barrier of the filling level monitor to the transfer
position is occupied with material, the sliding floor is
switched off with a delay by this set value.
Maximum runtime sliding floor
If the filling level monitor to the transfer position detects no
material in the system within the set time, the system shuts
down.
Sliding floor permanently active
If this parameter is activated, the sliding floor always feeds
upon material transport, even if the boiler is not requesting
material. The parameter is then used when two material
consumers (e.g. multi-boiler systems) should be filled.
5
Menus and parameters
Fuel feed
60