Completing the parameter settings
After setting the parameters, you must restart the frequency converter to apply the new settings.
NOTICE
Malfunctions after setting parameters!
If the frequency converter becomes inoperable after setting the required parameters:
❒ Perform a factory reset
❒ Set the parameters again
➥ The “Start”, “Back” and “Stop” buttons and the “potentiometer” usually have no function
after the frequency converter has been programmed.
You can restore the factory settings by setting parameter P 112 to 1. The parameter then automatically returns
to the value 0 and the frequency converter displays the message "F048".
Electric components and wiring
7
Frequency converter
Service manual SPS 4000 | B0960622_en
137