Technical data
32
– EN
ACT VS 3000 - 6000
11.15.10
Displaying technical maintenance and energy savings data
1-
With the dryer stopped (STANDBY) or operating (ON mode), press the
button to access the dryer's menu of functions.
2-
Press the
button to display:
➢
2a-
The total percentage of energy savings for the dryer, with respect to
its continuous operation at 100%.
➢
2b-
The partial percentage (starting from the last time the counter was
zeroed) of energy savings for the dryer, with respect to its continuous
operation at 100%.
➢
2c-
The date the partial energy savings counter was last zeroed.
➢
2d-
The total hours of dryer operation.
➢
2e-
The total hours of variable speed compressor operation.
➢
2f-
The total hours of 1st fixed speed compressor operation (if installed).
➢
2g-
The total hours of 2nd fixed speed compressor operation (if installed).
➢
2h-
The hours remaining till the next service.
➢
2i-
The partial hours of dryer operation, starting from the last time the
counter was zeroed.
NOTE!
Only qualified skilled personnel should perform following operations
3-
With dryer stopped (STANDBY mode), press the Reset button to reset the
count of the hours remaining before the next service (parameter SrV
→
default 8000 hours). This function is useful in the case of maintenance
carried out on the dryer before the hours remaining till the next service have
lapsed. This is a password-protected function (password code 3333) to
prevent the counter being reset accidentally.
4-
Press the Reset button to zero the partial energy savings counter.
5-
Confirm the counter is to be zeroed with OK, or exit without zeroing with
Cancel.
6-
Press the
button to return to the previous screen at any time.
1-
2-
3-
4-
2a-
2b-
2c-
2d-
2e-
2f-
2g-
2h-
2i-
5-
6-