Installation
ACT VS 3000 - 6000
EN - 15
8.4
Connection to the compressed air system
DANGER!
Compressed air!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The operator or the user must ensure that the dryer is never operated with a pressure exceeding the
maximum pressure value indicated on the name plate.
Exceeding the maximum operating pressure can be dangerous for the operator but also for the device.
The air temperature and the flow entering the dryer must comply within the limits stated on the data nameplate. The
system connecting piping must be kept free from dust, rust, chips and other impurities, and must be consistent with the
flow-rate of the dryer. In case of treatment of air at particularly high temperature, the installation of a final refrigerator
could result necessary. In order to perform maintenance operations, it is recommended to install a dryer by-pass
system. In realising the dryer, particular measures have been taken in order to limit the vibration which could occur
during the operation. Therefore we recommend to use connecting pipes able to insulate the dryer from possible
vibrations originating from the line (flexible hoses, vibration damping fittings, etc.).
NOTE!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (5 micron minimum), to avoid clogging of the heat
exchanger.