background image

17

920-087-06

Digital Control User Input Con

fi

 guration

The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center.  The inputs are only visible 
and accessible with the front cover removed from the PTAC.

Dip Switch Setting

1) Electronic Temperature Limiting – Switches 1-4

The digital control is set from the factory to allow a tempera-
ture range between 60°F and 90°F in both heating and cooling 
mode. Dip Switches 1-4 can be used to set high and low limits 
for either heating or cooling or both.
From the factory all four switches are in the up 

‘ON’

 position. The 

charts to the right show the available electronic limiting ranges.

2) Fan Cycle Control – Switch 5

All PTACs are shipped from the factory with Dip Switch 5 in the 

OFF

’ position to cycle the fan only when there is a demand for 

the compressor or heater. As an option the fan may be set to 
‘continuous’ mode by switching Dip Switch 5 to

 ‘ON’ 

position to 

run the fan continuously while the unit is powered on. 
To ensure that the room temperature is maintained evenly while 
in fan cycle mode the 

Even Temp Load Anticipation

 feature is 

enabled. 

Quiet Fan Delay

 is also enabled in fan cycle mode to 

lessen the acoustical change between compressor start up and 
shut off by running the fan for 5 seconds before each demand cycle, 
and 30 seconds after cooling or 15 seconds after heating cycles.

3) Room Freeze Protection – Switch 6

Units are shipped from the factory with the room freeze protection 
disabled. Room Freeze Protection can be switched on at the 
owner’s preference by moving Dip Switch 6 to

 ‘ON’

. This feature 

will monitor the indoor room conditions and in the event that the 
room falls below 40°F the unit will cycle on high fan with the 
electric heater. This occurs regardless of mode.

4) Emergency Heat Override – Switch 7

In the unlikely event of a compressor failure a heat pump unit 
may be switched to operate in only the electric heat mode until 
repairs can be made. Moving Dip Switch 7 to 

‘ON’

.

PTAC must be disconnected from power supply 
when making any con

fi

 guration changes.

Temperature 

Range

Dip 

Switch

Low

High

3

4

60

90

On

On

63

90

On

Off

66

90

Off

Off

69

90

Off

On

Cooling Range Switches 3 & 4

Heating Range Switches 1 & 2

Temperature 

Range

Dip          

Switch

Low

High

1

2

60

90

On

On

60

87

Off

On

60

84

Off

Off

60

81

On

Off

Digital Control Operation

Temperature Display

The Friedrich digital PTAC is shipped from the factory to display 
the desired room temperature on the LED readout. 
The unit can be con

fi

 gured to display the room temperature by 

simultaneously pressing the ‘

Cool

’ and ‘

High Fan

’ buttons 

for three seconds the display will show an ‘

R

’ for one seconds 

to acknowledge the change. The unit will display the setpoint 
whenever the ‘Temp’    or     buttons are pressed and then 
switch back to room temperature.
To revert back to displaying the setpoint only press the ‘

Cool

’ and 

Low Fan

’ buttons for three seconds simultaneously, the unit will 

display an ‘

S

’ for one seconds to acknowledge the change.

˚

F vs. 

˚

C Display

The unit is factory con

fi

 gured to display all temperatures in 

degrees Fahrenheit (

º

F

). To switch to degrees Celsius press 

the ‘

Fan Only

’ and 

‘Low Fan’

 buttons simultaneously for three 

seconds. The display will show a ‘

C

’ as acknowledgement of 

the change.
To revert back to 

º

F press the ‘

Fan Only

’ and 

Low Fan

’ buttons 

simultaneously for three seconds. The display will show an ‘

F

’ 

as acknowledgement of the change.

Figure 11  

Factory Dip Switch Con

fi

 guration

1 2 3 4 5 6 7 8

O

N

IMPORTANT

Summary of Contents for PDH07K3SB1

Page 1: ...920 087 06 4 08 PTAC PACKAGED TERMINAL AIR CONDITIONERS HEAT PUMPS Standard Control Remote Thermostat Seacoast Protected INSTALLATION OPERATION GUIDE...

Page 2: ...trol Diagnostics and Test Mode 26 Accessories 27 28 Warranty 29 Table of Contents Your safety and the safety of others are very important CAUTION NOTICE We have provided many important safety messages...

Page 3: ...3 920 087 06 Typical Unit Components Front cover Chassis Wall sleeve Outdoor grille...

Page 4: ...and install the equipment Installation must be in conformance with the NFPA 70 2008 National Electric Code or current edition and Uniform Mechanical Code current edition and applicable local or natio...

Page 5: ...AC units should be installed no closer than 12 apart when two units are side by side If three or more PTAC units are to operate next to one another allow a minimum of 36 between units Also a vertical...

Page 6: ...new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating problems The internal diagnostic program saves properties valuable time whe...

Page 7: ...cause the indoor coil to freeze When the indoor coil reaches 30 F the compressor is diabled and the fan continues to operate based on demand Once the coil temperature returns to 45 F the compressor re...

Page 8: ...locally to connect the internal drain tube to the drain system in the building 6 Referring to Detail A on page 9 locate and assemble the 2 two cover plates and gaskets over the drain holes at the rear...

Page 9: ...ard the wall sleeve 3 Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve The large flange on the mounting plate is positioned at the bottom of the sleeve facin...

Page 10: ...e higher than the back Electrical shock hazard Turn electric power OFF at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before co...

Page 11: ...re not followed Figure7 NOTE Construct wall opening to comply with all applicable building codes Main studs Jack studs Main studs Jack studs Lintel Mounting screw holes No holes in bottom of wall slee...

Page 12: ...Secure the wall sleeve extension to the wall sleeve before installing it in the wall Refer to Figure 8 for a guide for fabrication ofacondensatedrippanel ThepanelMUSTextendthefulldepth of the wall sl...

Page 13: ...outs facing down From inside the building maneuver the grille through the wall sleeve and pull toward you until the screw heads are inserted into the keyhole slots at the top of the wall sleeve Tighte...

Page 14: ...eets the UL and NEC requirements for cord connected air conditioners effective August 2004 To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet 2 Press RESET 3 Press...

Page 15: ...ressor Chassis shipping bracket Shipping pallet IMPORTANT WheninstallingaFriedrichP SeriesPTACintoan existing sleeve it is important to ensure that the unit is installed completely Inspection of the a...

Page 16: ...g brackets on the wall sleeve flange two per side 6 Install the front cover assembly including the discharge grille by placing the top of the cover onto the 90 angle bracket along the top of the chass...

Page 17: ...onditions and in the event that the room falls below 40 F the unit will cycle on high fan with the electric heater This occurs regardless of mode 4 Emergency Heat Override Switch 7 In the unlikely eve...

Page 18: ...mergencyHeatOperation In the event of a compressor failure in heat pump mode the com pressormaybelockedouttoprovideheatthroughtheresistance heater This feature ensures that even in the unlikely event...

Page 19: ...ommand to the PTAC unit The remote signal has some ability to bounce off of walls and furniture similar to a television remote control The diagram below shows the typical operating range of the contro...

Page 20: ...To revert back to the Smart Center control of the unit replace the jumper wire between the GL and GH terminals that was removed in step 1 ThermostatConnections C Common Ground W Call for Heating Y Cal...

Page 21: ...r tampering with the unit s internal wiring can void the equipmentwarrantyandmayresultinpropertydamage personal injury or death Other manufacturer s PTACs and even older Friedrich models may have diff...

Page 22: ...ure components and accessories such as the control door and front cover Check the unit air filter condenser coil and evaporator coil for any obstructions Check for proper operation of all components I...

Page 23: ...maintenance and service to the chassis Line Voltage Connections Figure18 5 Make the appropriate electrical connections within the control box then secure the box on the chassis Detailed instructions a...

Page 24: ...coil cleaning agent on coils or base pan Use a biodegradable cleaning agent and degreaser NOTE Units are to be inspected and serviced by qualified service personnel only Discharge Air Grille Filters...

Page 25: ...for proper sizing Istheoutdoortemperature60 Forbelow The unit is designed for outdoor temperatures above 60 F Istheindoortemperature80 Forabove Ambient indoor temperatures of 80 F or above will take...

Page 26: ...rror code Leave unit running Defective sensor 05 Outdoor coil thermistor sensor open Or short circuit Set OD coil temp 20 F Alternately flash set point and error code Automatically change over to Elec...

Page 27: ...to the outside of the wall sleeve when the wall is greater than 11 inches thick 9 when a subbase is used 10 inches when a lateral duct is used Up to three exten sions my be used together PXSB DECORAT...

Page 28: ...r The extension can be cut to length by the installer Maximum allowable straight extension is 15 feet PXCJ CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208 230V and 265V u...

Page 29: ...sented to establish the original purchase date otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days Replacement parts can be new or remanufacture...

Reviews: