GENERAL
This INSTALLATION MANUAL briefly outlines where
and how to install the air conditioning system. Please
read over the entire set of instructions for the indoor
and outdoor units and make sure all accessory parts
listed are with the system before beginning.
1. TYPE OF COPPER PIPE AND INSULATION MATERIAL
Copper tubing for connectin the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
A. Deoxidized annealed copper pipe for refrigerant piping as:
Table 4
Name and Shape
Wall hook bracket
Remote
control
unit
Battery (penlight)
Remote control
unit holder
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as
required.
Q’ty
1
1
2
1
Name and Shape
Cloth tape
Tapping screw (big)
Tapping screw (small)
Drain pipe
Connection pipe assembly
Connection cord (3-conductor)
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
Name
Q’ty
1
1
1
1
1
1
1 set
1
1 set
1
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch cir-
cuit and provide a special switch and receptacle. Do not extend the
power cord.
Always select the size that corresponds to the capacity of the breaker to
the size of the power cord.
The following items are necessary to install this air conditioner. (The
items are not included with the air conditioner and must be purchased
separately.)
CAUTION
9000 BTU/h 12000 BTU/h
MINIMUM CIRCUIT AMPACITY
10 A
12 A
MAXIMUM OVERCURRENT PROTECTION
15 A
15 A
(TIME DELAY FUSE OR HACR TYPE CIRCUIT BREAKER)
Cut each pipe to the appropriate 12” (30 cm)
to16” (40 cm) to dampen vibration between units.
B. Foamed polyethylene insulation for copper pipes as
required to precise length of piping. Wall thickness
of the insulation should not be less than 5/16” (8 mm).
C. Use insulated copper wire for field wiring.
CAUTION
Check local electrical codes and regulations
before obtaining wire. Also, check any specified
instructions or limitations.
2. ADDITIONAL MATERIALS REQUIRED FOR INSTALLATION
A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
3. OPERATING RANGE
Table 5
ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 49 ft (15 m) is charged in
the outdoor unit at the factory.
When the piping is longer than 49 ft (15 m), additional charging is necessary.
For the additional amount, see the table below.
Between 49 ft (15 m) and 66 ft (20 m), when using a connection pipe
other than that in the table, charge additional refrigerant with 0.2 oz/
ft (20g/1 m) as the criteria.
Pipe length
Additional
refrigerant
49 ft (15 m)
None
Table 6
66 ft (20 m)
3.5 oz (100 g)
CAUTION
(1) When adding refrigerant, add the refrigerant from
the charging port at the completion of work.
(2) The maximum length of the piping is 66 ft (20 m).
If the units are further apart than this, correct
operation can not be guaranteed.
Heating Mode
About 5 to 75 °F
86 °F or less
Outdoor temperature
Indoor temperature
Indoor humidity
Cooling/Dry Mode
About 14 to 115 °F
About 64 to 90 °F
About 80% or less
Small pipe
Large pipe
Outer diameter
Thickness
Outer diameter
Thickness
1/4”(6.35 mm)
1/32”(0.8 mm)
3/8”(9.52 mm)
1/32”(0.8 mm)
Q’ty
1
8
2
1