Friedrich M12YG Installation Manual Download Page 6

For left piping and left rear piping, align the marks on the wall
hook bracket and shape the connection pipe.

Bend the connection piping at a bend radius of 2 - 3/4’’(70 mm) or
more and install no more than 1- 3/8’’(35 mm) from the wall.

After passing the indoor piping and drain hose through the wall
hole, hang the indoor unit on the hooks at the top and bottom of
the wall hook bracket.

[Installing the indoor unit]

Hang the indoor unit from the hooks at the top of the wall hook
bracket.

Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.

Fig. 4

After hooking the indoor unit to the top hook, hook the fittings of the
indoor unit to the two bottom hooks while lowering the unit and
pushing it against the wall.

BENDING PIPES

The pipes are shaped by your hands. Be careful not to collapse them.

Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or stretch
the pipes more than three times.

Top hooks

Indoor unit

Bottom hooks

Wall hook bracket

Connection pipe
(1/4” (6.35  mm)
dia.)

Connection pipe
 (3/8” (9.52 mm) dia.)

Align the marks.

Bend (R70) with
a pipe bender

Indoor unit

Wall hook bracket

(Spacer)

CONNECTION

(1) Install the outdoor unit wall cap (supplied with the optional installa-

tion set or procured at the site) to the wall pipe.

(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the nut

hand tight, tighten the nut to the specified tightening torque with a
torque wrench. (Table 2)

FLARING

(1) Cut the connection pipe to the nec-

essary length with a pipe cutter.

(2) Hold the pipe downward so that

cuttings will not enter the pipe and
remove the burrs.

(3) Insert the flare nut onto the pipe

and flare the pipe with a flaring
tool.

Insert the flare nut (always use the flare
nut attached to the indoor and outdoor
units respectively) onto the pipe and
perform the flare processing with a
flare tool.
Use the special R410A  flare tool, or
the conventional (for R22) flare tool.
When using the conventional flare tool,
always use an allowance adjustment
gauge and secure the A dimension
shown in table 3 .

CONNECTING THE PIPING

Check if [L] is flared uniformly
and is not cracked or scratched.

Table 2

Flare nut tightening torque

Table 3

Pipe outside diameter

Flare nut

1/4” (6.35  mm) dia.

3/8” (9.52  mm) dia.

Tightening torque

11.57 to 13.20 ft

lbs

(160 to 180 kgf

cm)

21.70 to 30.38 ft

lbs

(300 to 420 kgf

cm)

A (in)

Pipe outside

diameter

1/4” (6.35 mm)

3/8” (9.52 mm)

Flare tool for

R410A, clutch type

0 to 1/32

0 to 1/32

Conventional (R22) flare tool

Clutch type

1/32 to 2/32

1/32 to 2/32

Wing nut type

2/32 to 3/32

2/32 to 3/32

CAUTION

(1) Fasten a flare nut with a torque wrench as instructed in this manual. If

fastened too tight, the flare nut may be broken after a long period of time
and cause a leakage of refrigerant.

(2) During installation, make sure that the refrigerant pipe is attached firmly

before you run the compressor. Do not operate the compressor under the
condition of refrigerant piping not attached properly with 2-way or 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to breakage and even injury.

Fig. 5

Tighten with two wrenches.

Torque
wrench

Wrench (fixed)

Flare nut

Indoor unit pipe

Connection pipe

To prevent gas leakage, coat the flare
surface with refrigerator oil.

Die

A

Pipe

OK

NO

Extend the pipe
by unwinding it.

Summary of Contents for M12YG

Page 1: ...tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help...

Page 2: ...8 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detec...

Page 3: ...ELAY FUSE OR HACRTYPE CIRCUIT BREAKER Cut each pipe to the appropriate length 12 30 cm to16 40 cm to dampen vibration between units B Foamed polyethylene insulation for copper pipes as required to pre...

Page 4: ...he danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit 4 Install t...

Page 5: ...ozen under low tempera ture environment When installing indoor unit s drain hose outdoors necessary measure for frost protection should be taken to prevent drain water frozen Under low temperature env...

Page 6: ...ut the connection pipe to the nec essary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare...

Page 7: ...ve blank cap and the charging port cap 7 Pump down the system for at least 15 minutes then check if the compound pressure gauge reads 0 1 MPa 76 cmHg 1 bar 8 At the end of pump down close the low pres...

Page 8: ...erminal to over heat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trad...

Page 9: ...ws to install the cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 U...

Page 10: ...ulation Vinyl tape Pipe Drain hose Cloth tape Wrap with cloth tape Left piping Connection cord Pipe Drain hose For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe Dr...

Page 11: ...al branch circuit and install a special receptacle to supply power to the room air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 Do not extend the...

Page 12: ...djusting inter unit wire harness To connect inter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit hold...

Page 13: ...e remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control unit holder fixing Remote control unit...

Reviews: