Friedrich M12YG Installation Manual Download Page 2

5 cm or over

The basic installation work procedures are the same as conventional refrigerant (R22) models.

 However, pay careful attention to the following points:

(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant(R22) mod-

els, some of the piping and installation and service tools are special.(See the table below.)

Especially, when replacing a conventional refrigerant(R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.

(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent

erroneous charging with conventional refrigerant(R22) and for safety. Therefore, check
beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]

(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with

refrigerant(R22) models. Also, when storing the piping ,securely seal the opening by pinching,
taping, etc.

(4) When charging the refrigerant, take into account the slight change in the composition of the

gas and liquid phases, and always charge from the liquid phase side whose composition is
stable.

This air conditioner uses new refrigerant HFC (R410A).

Special tools for R410A

Contents of change

Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
mixing of other refrigerants, the diameter of each port has been changed.

It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.

-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

To increase pressure resistance, the hose material and base size were changed.

A conventional vacuum pump can be used by installing a vacuum pump adapter.

Special gas leakage detector for HFC refrigerant R410A.

Tool name

Gauge manifold

Charge hose

Vacuum pump

Gas leakage detector

Copper pipes

It is necessary to use seamless copper pipes and it is desirable
that the amount of residual oil is less than 40 mg/10m. Do not
use copper pipes having a collapsed, deformed or discolored
portion (especially on the interior surface). Otherwise, the ex-
pansion value or capillary tube may become blocked with con-
taminants.
As an air conditioner using R410A incurs pressure higher than
when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table1.Never use copper pipes thinner than 0.8mm even
when it is available on the market.

Table 1   Thicknesses of Annealed Copper Pipes

Thickness (mm)

Nominal

diameter

1/4

3/8

Outer diameter

(mm)

6.35

9.52

R410A

0.80

0.80

[ref.] R22

0.80

0.80

(1) Do not use the existing (for R22) piping and flare nuts.

• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury,

etc.(Use the special R410A materials.)

(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)

to enter the refrigerant cycle.

• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value

and cause breakage, injury, etc.

 WARNING

CAUTION

When installing pipes shorter than 10ft (3m), sound of the outdoor unit will be transferred to the indoor unit, which
will cause large operating sound or some abnormal sound.

Summary of Contents for M12YG

Page 1: ...tightly Loose wiring may cause overheating at con nection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help...

Page 2: ...8 bar for low pressure To increase pressure resistance the hose material and base size were changed A conventional vacuum pump can be used by installing a vacuum pump adapter Special gas leakage detec...

Page 3: ...ELAY FUSE OR HACRTYPE CIRCUIT BREAKER Cut each pipe to the appropriate length 12 30 cm to16 40 cm to dampen vibration between units B Foamed polyethylene insulation for copper pipes as required to pre...

Page 4: ...he danger of com bustible gas leakage 2 Do not install near heat sources 3 If children under 10 years old may approach the unit take preventive measures so that they can not reach the unit 4 Install t...

Page 5: ...ozen under low tempera ture environment When installing indoor unit s drain hose outdoors necessary measure for frost protection should be taken to prevent drain water frozen Under low temperature env...

Page 6: ...ut the connection pipe to the nec essary length with a pipe cutter 2 Hold the pipe downward so that cuttings will not enter the pipe and remove the burrs 3 Insert the flare nut onto the pipe and flare...

Page 7: ...ve blank cap and the charging port cap 7 Pump down the system for at least 15 minutes then check if the compound pressure gauge reads 0 1 MPa 76 cmHg 1 bar 8 At the end of pump down close the low pres...

Page 8: ...erminal to over heat or result in unit malfunction A fire hazard may also exist Therefore be sure all wiring is tightly connected Connect wires to the matching numbers of terminals NOTE Connector trad...

Page 9: ...ws to install the cord clamp A For solid core wiring or F cable 1 Cut the wire end with a wire cutter or wire cutting pliers then strip the insulation to about 15 16 25 mm to expose the solid wire 2 U...

Page 10: ...ulation Vinyl tape Pipe Drain hose Cloth tape Wrap with cloth tape Left piping Connection cord Pipe Drain hose For connection from the left rear Connection cord Drain hose Wall pipe Connection pipe Dr...

Page 11: ...al branch circuit and install a special receptacle to supply power to the room air conditioner 4 Use a circuit breaker and receptacle matched to the capacity of the air conditioner 5 Do not extend the...

Page 12: ...djusting inter unit wire harness To connect inter unit wire harness to the terminal correctly please refer to Fig 19 to adjust the length of the part of Inter unit Wire harness ahead from conduit hold...

Page 13: ...e remote con trol unit check that it operates positively Install the remote control unit holder to a wall pillar etc with the tapping screw Fig 20 Remote control unit holder fixing Remote control unit...

Reviews: