Measuring

Measuring q

1. Remove any actuator.
2. Connect IMI TA* balancing instrument to 
the measuring points.
3. Input the valve type, size and setting and 
the actual flow is displayed.

Measuring 

D

H

1. Remove any actuator.
2. Close the valve according to “Shut-off”.
3. Bypass the 

D

p part by opening the bypass 

spindle 

1 turn anticlockwise, with a 5 mm 

Allen key.
4. Connect IMI TA* balancing instrument to 
the measuring points and measure.

Important!

 Close the bypass spindle after the 

measurement is completed.

Leakage rate:

Leakage flow 

 0,01% of max. q

max

 (setting 10) 

and correct flow direction.
(Class IV according to EN 60534-4).

Connection:

Male thread according to ISO 228.

Marking

TA, IMI, PN 16, DN and flow direction
arrow. Grey setting wheel: TA-COMPACT-P 
and DN. For low flow version also LF.

Application

The regulation and adjustment valve (TAC) 
can be used to finely adjust or shut off the 
water flow manually. TAC is independent 
of the available differential pressure, which 
contributes to stable and accurate regulation 
(ensures the correct flow to the heater even if 
the differential pressure in the rest of the pipe 
system changes). The water flow is set using 
the gray adjustment knob on the valve.
 

Functions

•  Control
•  Pre-setting (max. flow)
•  Differential pressure control
•  Measuring (

D

H, T, q)

•  Shut-off

Noise

In order to avoid noise in the installation 
the valve must be correctly installed and the 
water de-aerated.

* www.imi-hydronic.com/

Summary of Contents for VLSP Series

Page 1: ...VLSP 2 SE 9 GB SD230 AV BPV10 SD230 TAC AV BPV10 16 NO 23 DE 30 FR 37 NL 44 ES 51 RU TAC...

Page 2: ...Shut off valve DN15 BPV10 By pass valve DN10 VLSP15NF Type Specification TAC20 Two way pressure independent regulation and adjustment valve Normal flow DN20 SD230 Actuator on off 230V 230V AV20 Shut...

Page 3: ...he available differential pressure which contributes to stable and accurate regulation ensures the correct flow to the heater even if the differential pressure in the rest of the pipe system changes T...

Page 4: ...Flow range The flow qmax can be set within the range DN 15 LF 44 245 l h DN 15 NF 88 470 l h DN 20 210 1150 l h DN 25 370 2150 l h DN 32 800 3700 l h qmax l h at each setting and fully open valve plu...

Page 5: ...EN 60534 4 Connection Male thread according to ISO 228 Marking TA IMI PN 16 DN and flow direction arrow Grey setting wheel TA COMPACT P and DN For low flow version also LF Application The regulation a...

Page 6: ...um flow deviation at different settings Setting of fully open valve Shut off 1 Turn the setting wheel clockwise to X 0 2 4 6 8 10 12 14 16 18 20 22 24 0 20 40 60 80 100 10 30 50 70 90 qmax values 1 2...

Page 7: ...ified force actuator without exceeding stated leakage rate pVmax The maximum allowed pressure drop over the valve to fulfill all stated performances 22 10 X M30x1 5 Shut off valve AV15 20 25 32 Dimens...

Page 8: ...chnical specifikations Application The electrical actuator in combination with the valve is used for regulating the heat supply to the unit It s function is to open or close the valve on off In unpowe...

Page 9: ......

Page 10: ......

Page 11: ...fice Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E4593 2016...

Reviews: