VLSP,  pressure independent 
valve kit on/off

Two way pressure independent control and 
adjustment valve with on/off actuator, shut-off 
valve and bypass. DN15/20/25/32. 230V.

The valve set consists of the following:
•  TAC, pressure independent regulation and 

adjustment valve

•  SD230, actuator on/off 230V
•  AV, shut off valve
•  BPV10, bypass valve

The shut off valve (AV) consists of a ball valve 
which is either open or closed and is used to 
shut off the flow, when servicing for example.

The regulation and adjustment valve (TAC) 

can be used to finely adjust or shut off the 
water flow manually. TAC is independent 
of the available differential pressure, which 
contributes to stable and accurate regulation 
(ensures the correct flow to the heater even if 
the differential pressure in the rest of the pipe 
system changes). The water flow is set using 
the gray adjustment knob on the valve

If the valve (TAC) is closed, a low flow 

passes through the by-pass valve (BPV10) so 
that there is always hot water in the water 
coil. This is to provide quick heat supply 
when a door is opened but also to provide a 
degree of frost protection.

The actuator (SD) controls the heat supply 

on/off. In unpowered mode SD230 is open.

The valve set is available in 4 different 

valve dimensions, DN15 (1/2"), DN20 (3/4"), 
DN25 (1") and DN32 (1 1/4"). The by-pass 
valve is DN10 (3/8").

Used with SIRe Basic and Competent or 

supplemented with suitable thermostat.

SD230

TAC

AV

BPV10

Summary of Contents for VLSP Series

Page 1: ...VLSP 2 SE 9 GB SD230 AV BPV10 SD230 TAC AV BPV10 16 NO 23 DE 30 FR 37 NL 44 ES 51 RU TAC...

Page 2: ...Shut off valve DN15 BPV10 By pass valve DN10 VLSP15NF Type Specification TAC20 Two way pressure independent regulation and adjustment valve Normal flow DN20 SD230 Actuator on off 230V 230V AV20 Shut...

Page 3: ...he available differential pressure which contributes to stable and accurate regulation ensures the correct flow to the heater even if the differential pressure in the rest of the pipe system changes T...

Page 4: ...Flow range The flow qmax can be set within the range DN 15 LF 44 245 l h DN 15 NF 88 470 l h DN 20 210 1150 l h DN 25 370 2150 l h DN 32 800 3700 l h qmax l h at each setting and fully open valve plu...

Page 5: ...EN 60534 4 Connection Male thread according to ISO 228 Marking TA IMI PN 16 DN and flow direction arrow Grey setting wheel TA COMPACT P and DN For low flow version also LF Application The regulation a...

Page 6: ...um flow deviation at different settings Setting of fully open valve Shut off 1 Turn the setting wheel clockwise to X 0 2 4 6 8 10 12 14 16 18 20 22 24 0 20 40 60 80 100 10 30 50 70 90 qmax values 1 2...

Page 7: ...ified force actuator without exceeding stated leakage rate pVmax The maximum allowed pressure drop over the valve to fulfill all stated performances 22 10 X M30x1 5 Shut off valve AV15 20 25 32 Dimens...

Page 8: ...chnical specifikations Application The electrical actuator in combination with the valve is used for regulating the heat supply to the unit It s function is to open or close the valve on off In unpowe...

Page 9: ......

Page 10: ......

Page 11: ...fice Frico AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E4593 2016...

Reviews: