VLSP
14
GB
Closing force
Working range: X (closed - fully open) =
11,6 - 15,8
Closing force: Min. 125 N (max. 500 N)
The maximum recommended pressure drop
over a valve and actuator combination for
close off (
D
pV
close
) and to fulfill all stated
performances (
D
pV
max
).
kPa*
DN15
400
DN20
400
DN25
400
DN32
400
*) Closing force 125 N.
D
pV
close
= The maximum pressure drop that
the valve can close against from an opened
position, with a specified force (actuator)
without exceeding stated leakage rate.
D
pV
max
= The maximum allowed pressure
drop over the valve, to fulfill all stated
performances.
Ø22
10
X
M30x1,5
Shut off valve (AV15/20/25/32)
Dimensions and technical specifikations
A
B
C
D
Application
The shut off valve is used to shut off the water
flow to the unit and consists of a ball valve
which is either open or closed. The shut off
valve have no adjustment function and is only
used for maintance and service.
Type
DN
A
[mm]
B
[mm]
C
[mm]
D
[mm]
Weight
[kg]
AV15
15
119
57
25
57
0,2
AV20
20
130
57
32
70
0,3
AV25
25
140
62
42
85
0,3
AV32
32
178
81
57
104
0,5