GB
17
Mounted on board it can control the motor; with modular
speed; the motor regulation can be done through a 0-10
V DC analogue input with 25 kΩ input impedance.
Consider this impedance value for the control outputs to
B10642, especially if you want to control several units in
parallel.
It has a 230 V output for driving solenoid.
Installation of control for remote operation (B10642) model R1
Mounting and connecting the fan control for remote adjustment B10642
Mounting
A
H
I
D
E
C
G
B
F
L
Place the control panel into its housing in the upper
part of the device and fix it with the two supplied screws
(ref. A).
To install the connection box:
- open the box (ref. B);
-
insert the lower lug into the special slot (ref. C) on the
side of the appliance;
- hook the upper part of the box to the side (ref. D);
- fix it with the two supplied screws (ref. E);
- fix the earth wire to the cooler-convector/cooler-
radiator structure using the supplied screws (the
minimum force of about 2N must be used when
screwing-up);
- the 2 terminals of the GRID clamp (ref. I) feature a
jumper that ensures the operation of the SLI and RSI
versions without microswitch.
For the other versions remove the jumper and
connect the two terminals from the grid safety
microswitch. * ;
- connect the rapid connector on the motor (MOTOR)
to that on the board (ref. H);
- make the electrical connections, order the wiring
and fix the wires using the 3 supplied clamps (ref.
F);
- close the box and fix with the 4 screws (ref. G);
- mount the aesthetic side panel on the Cooler-
convector/cooler-radiator;
- tighten the upper screw on the control panel;
- place the screw cover into the slot on blind panel.
The LED (ref. L) is off if the input signal is below 0.9 V.
It is switched on for values over 1 V and signals standard
operation.
•
Flashes frequently if the S1 grill safety microswitch
is enabled due to a filter cleaning operation.
•
2 f pause for motor alarm (for example
jamming due to foreign bodies or fault in the rotation
sensor).
LED signals