Alarm and error codes

SIRe has different alarms and error codes for 
safe and problem free operation.

If alarms or error codes have been indicated 

these must be reset in order to return to 
normal operation, for example activating the 
heating again. Fan mode is active even when, 
for example, the over heating alarm has been 
indicated.

Displaying alarm and error codes

In event of alarm or error the alarm/error 
code is shown in the status window. In event 
of alarm/error code the unit it applies to is 
displayed. See 

Table - Alarms

 and 

Table – 

Error codes

.

Reset alarm

Note! Before resetting, check that the fault is 
rectified and there is nothing to prevent the 
unit from being recommissioned!

When the fault is rectified, the alarm is reset 
by pressing the forward arrow and selecting 

Reset alarm

 and then confirm. If several units 

give an alarm at the same time, the fact that 
there are several alarms is indicated, but only 
one is shown in the display. By resetting that 
alarm the next alarm can be read.

Overheat protection

Only applies to units with internal sensor.
The over heating protection is intended to 
restrict the exhaust temperature to 40°C. At 
40°C the valve actuator closes. If the unit 
cools below +35 °C, heating is automatically 
reengaged. If the temperature should instead 
continue to rise, e.g. in the event of a faulty 
valve or actuator, the fan starts to speed up at 
46 °C to keep the temperature down. At the 
same time there is an over heating alarm 

A2

At internal temperatures of 50 °C the fan runs 
at maximum speed.

If the unit cools below 35 °, heating is 

automatically reengaged.  The alarm remains 
in the control unit’s display. If the unit 
overheats twice within an hour, the fan 
operates until the alarm is reset.

Power failure

Note that in case of power failure the time 
settings need to be checked, if the time is not 
set correctly week program will be affected.

Frost protection function

Only applies to units with internal sensor. 
The frost protection function is intended 
to prevent the water coil from freezing. If 
the internal temperature falls below +5 °C 
frost protection alarm 

A3

 is given, the valve 

actuator opens and the fan stops.

Note! In event of repeated alarms, 

overheating alarms and frost protection 
alarms, carry out a thorough check and if 
the fault cause cannot be found contact 
authorised service personnel or Frico.

Summary of Contents for SIReAC

Page 1: ...19 GB 2 SE For more languages please see www frico se For wiring diagram please see p 71 73 SIRe Competent Air Curtains Water With quick guide SIReAC Original instructions 54 FR 36 DE...

Page 2: ...ReC1X with RJ12 modular cables In SIReB1 X the unit is also connected further with RJ12 modular cable if several units are to be connected in parallel If external room temperature sensor SIReRTX optio...

Page 3: ...t open for longer periods 24 25 Function description of current stage 25 26 Control unit SIReUA1 Overview 27 Main menu Current settings 28 Temp settings 28 Fan control 28 Summer Winter 28 System on of...

Page 4: ...rts SIReAC Integrated in the air curtain Wall unit cover SIReIT internal temperature sensors SIReDC magnetic door contact Type Description HxWxD mm L m SIReUA1 Control unit Competent and Advanced 120x...

Page 5: ...maximum of 300 m Type RSK no E no Description HxWxD mm L m SIReRTX 673 09 22 87 510 12 External room temperature sensor 70x33x23 SIReUR 673 09 21 87 510 11 Kit for recessed installation 114x70x50 SIR...

Page 6: ...ow Connection VOS15LF 673 09 35 On off Low DN15 VOS15NF 673 09 36 On off Normal DN15 VOS20 673 09 37 On off Normal DN20 VOS25 673 09 38 On off Normal DN25 VOSP15LF 673 09 43 Pressure independent Low D...

Page 7: ...xternal room temperature sensor SIReRTX option When the door is closed over run When heat has been connected and the door has been closed high speed mode remains to cool the unit from any excess heat...

Page 8: ...e current settings the current stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer If summer mode is selecte...

Page 9: ...nt stage for units with 5 fan controls Current stage Fan Heating 0 0 OFF 1 1 OFF 2 2 OFF 3 2 ON 4 3 ON 5 3 ON Current stage Fan Heating 0 0 OFF 1 1 OFF 2 2 OFF 3 2 ON 4 3 ON 5 3 ON 6 4 ON 7 5 ON 8 5 O...

Page 10: ...ating step door status and day night mode or Off when the week program is used Forward arrow Confirm selection and proceed Rotary dial Scroll between alternatives Back arrow Go back After three minute...

Page 11: ...menu Fan control Factory setting High speed limit 3 resp 5 1 3 resp 1 5 Speed closed door 1 Off 3 resp Off 4 Summer Winter To permit or block heating Heating is permitted in winter mode Summer mode is...

Page 12: ...Day 4 16 00 Night Remove single Remove all Reset all Remove program Change program Mon Tue Wed Thu Fri Sat Sun 1 08 00 Day 2 18 00 Night 3 10 00 Day 4 16 00 Night Installer menu To enter the Installe...

Page 13: ...ttings Door over run Over run mode High speed over run Low speed over run Installer menu Fan settings Door over run Door over run Door mode Installer menu Fan settings Settings fan Make settings for f...

Page 14: ...sor displays the wrong values these can be calibrated Some display errors may occur but this is primarily due to the location cold hot surfaces etc The value or adds to or subtracts from the measured...

Page 15: ...al control General settings Support menu Installer menu Set date Set time Set language Installer menu General settings Set temp unit Function test User reset Installer menu General settings Execute us...

Page 16: ...nal sensor The over heating protection is intended to restrict the exhaust temperature to 40 C At 40 C the valve actuator closes If the unit cools below 35 C heating is automatically reengaged If the...

Page 17: ...ectified SIReUA1 must be replaced Table Error codes Alarm Cause Action A1 Motor alarm Thermal switch has deployed One or several motors have overheated Only units with withdrawn thermal switches Check...

Page 18: ...menu External control External On Off On External night reduction on off potential free switch Closes to activate the night reduction function Always active Alarm outgoing BMS potential free switch m...

Page 19: ...TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 1617...

Page 20: ...ial free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM...

Page 21: ...L N L PE ACTUATOR SUPPLY SIReSD230 SIReSD230 SIReSD230 SIReRTX optional SIReUA1 EXTERNAL SETBACK TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN E...

Page 22: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E44...

Reviews: