24

GB

Operating modes

Door that is opened and closed

The control function notes whether the door 
is open or closed as standard, this mode is 
default set and is called 

Fixed flexible

 (the 

setting is under 

Installer menu > Settings fan 

> Door mode

). 

Open door

Indicates ÖP on the installer status screen. 
The fan speed runs at high speed which is set 
under 

Main menu > Fan speed > Max fan 

speed

.

Normally it is requested that heat is engaged 
when the door is opened. The setpoint value 
(Room temp. day) is then increased with 
the fixed setpoint value difference that can 
be changed under 

Installer menu> Settings 

heating > Open door setp. diff., 

factory 

setting 3.0 K. The set point is set under 

Main 

Menu > Temperature settings > Room temp. 
day

. If week program is used the night time 

set point value is set under 

Main menu > 

Temp. settings > Room temperature night

The room temperature is measured using the 
integrated room temperature sensor or the 
external room temperature sensor, SIReRTX 
(option).  

Closed door

Indicated ST on the installer status screen. 
The fan speed runs at low speed which is 
set under 

Main menu > Fan speed > Speed 

closed door

Heating is regulated to Room temp. Day 
which is set under 

Main Menu > Temperature 

settings > Room temp. day

. If week program 

is used the night time set point value is 
regulated against the Room temperature is set 
under 

Main menu > Temp. settings > Room 

temperature night

. The room temperature 

is regulated using the integrated room 
temperature sensor or the external room 
temperature sensor, SIReRTX (option).  

When the door is closed - over run

When heat has been connected and the door 

has been closed, high speed mode remains to 
cool the unit from any excess heat during the 
fixed time that is set under  

Installer menu > 

Settings fan > Door over run > High speed 
over run 

 and at low speed during a fixed 

time under 

Installer menu > Settings fan> 

Door over run > Low speed over run 

, on 

the condition that it is sufficiently warm in 
the premises, otherwise the fans run until the 
desired temperature has been reached.
When the door is closed, the set point value 
shifts from room tempe fixed set point 
value difference for open door to Room temp. 
day/night.

Over run is factory set so that the over 
run times are controlled according to how 
often the door is opened (Auto mode under 

Installer menu > Settings fan > Over run 
door > Over run mode)

Doors that are always or often left open for 
longer periods

If a door is always, or often, left open it is 
possible to use a function called CURRENT 
STAGE instead.  The fan and heating steps 
increase/decrease 6 or 9 steps (depending on 
the type of unit) and are only controlled by 
the room temperature.

Current stage is activated in two ways:

Doors that are always open

For a door that is always open, door mode 

Locked open 

 can be selected under 

Settings 

fan> Door mode

.

Doors that are often open for longer 
periods

For a door that is often open  

Auto 

can be 

selected under 

Installer menu > Settings 

fan > Door mode

. In Auto mode, the control 

automatically switches between 

Flexible

 and 

open

 modes depending on how often the door 

has been open (when the door has been open 
for longer than 300 seconds the function 
changes from Flexible to Open).

Summary of Contents for SIReAC

Page 1: ...19 GB 2 SE For more languages please see www frico se For wiring diagram please see p 71 73 SIRe Competent Air Curtains Water With quick guide SIReAC Original instructions 54 FR 36 DE...

Page 2: ...ReC1X with RJ12 modular cables In SIReB1 X the unit is also connected further with RJ12 modular cable if several units are to be connected in parallel If external room temperature sensor SIReRTX optio...

Page 3: ...t open for longer periods 24 25 Function description of current stage 25 26 Control unit SIReUA1 Overview 27 Main menu Current settings 28 Temp settings 28 Fan control 28 Summer Winter 28 System on of...

Page 4: ...rts SIReAC Integrated in the air curtain Wall unit cover SIReIT internal temperature sensors SIReDC magnetic door contact Type Description HxWxD mm L m SIReUA1 Control unit Competent and Advanced 120x...

Page 5: ...maximum of 300 m Type RSK no E no Description HxWxD mm L m SIReRTX 673 09 22 87 510 12 External room temperature sensor 70x33x23 SIReUR 673 09 21 87 510 11 Kit for recessed installation 114x70x50 SIR...

Page 6: ...ow Connection VOS15LF 673 09 35 On off Low DN15 VOS15NF 673 09 36 On off Normal DN15 VOS20 673 09 37 On off Normal DN20 VOS25 673 09 38 On off Normal DN25 VOSP15LF 673 09 43 Pressure independent Low D...

Page 7: ...xternal room temperature sensor SIReRTX option When the door is closed over run When heat has been connected and the door has been closed high speed mode remains to cool the unit from any excess heat...

Page 8: ...e current settings the current stage increases by 1 step If the room temperature is more than 2 degrees above the current setting the current stage decreases by 1 step Summer If summer mode is selecte...

Page 9: ...nt stage for units with 5 fan controls Current stage Fan Heating 0 0 OFF 1 1 OFF 2 2 OFF 3 2 ON 4 3 ON 5 3 ON Current stage Fan Heating 0 0 OFF 1 1 OFF 2 2 OFF 3 2 ON 4 3 ON 5 3 ON 6 4 ON 7 5 ON 8 5 O...

Page 10: ...ating step door status and day night mode or Off when the week program is used Forward arrow Confirm selection and proceed Rotary dial Scroll between alternatives Back arrow Go back After three minute...

Page 11: ...menu Fan control Factory setting High speed limit 3 resp 5 1 3 resp 1 5 Speed closed door 1 Off 3 resp Off 4 Summer Winter To permit or block heating Heating is permitted in winter mode Summer mode is...

Page 12: ...Day 4 16 00 Night Remove single Remove all Reset all Remove program Change program Mon Tue Wed Thu Fri Sat Sun 1 08 00 Day 2 18 00 Night 3 10 00 Day 4 16 00 Night Installer menu To enter the Installe...

Page 13: ...ttings Door over run Over run mode High speed over run Low speed over run Installer menu Fan settings Door over run Door over run Door mode Installer menu Fan settings Settings fan Make settings for f...

Page 14: ...sor displays the wrong values these can be calibrated Some display errors may occur but this is primarily due to the location cold hot surfaces etc The value or adds to or subtracts from the measured...

Page 15: ...al control General settings Support menu Installer menu Set date Set time Set language Installer menu General settings Set temp unit Function test User reset Installer menu General settings Execute us...

Page 16: ...nal sensor The over heating protection is intended to restrict the exhaust temperature to 40 C At 40 C the valve actuator closes If the unit cools below 35 C heating is automatically reengaged If the...

Page 17: ...ectified SIReUA1 must be replaced Table Error codes Alarm Cause Action A1 Motor alarm Thermal switch has deployed One or several motors have overheated Only units with withdrawn thermal switches Check...

Page 18: ...menu External control External On Off On External night reduction on off potential free switch Closes to activate the night reduction function Always active Alarm outgoing BMS potential free switch m...

Page 19: ...TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 1617...

Page 20: ...ial free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN EXTERNAL ON OFF 5 30V AC DC ALARM OUT BMS potential free contact max 3A 230V 7 8 9 10 1112 15 161718 19 20 COM 1 COM...

Page 21: ...L N L PE ACTUATOR SUPPLY SIReSD230 SIReSD230 SIReSD230 SIReRTX optional SIReUA1 EXTERNAL SETBACK TEMP ON OFF potential free contact EXTERNAL ALARM IN potential free contact EXTERNAL RPM 0 10V DC IN E...

Page 22: ...B Tel 46 31 336 86 00 Box 102 Fax 46 31 26 28 25 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se Art no E44...

Reviews: