SIRe Competent Air Curtains Water
30
GB
Week program is activated by selecting On,
under Week program on/off. In On-mode,
a sun, moon or Off in the Status window
appears to indicate day, night respectively
Off-function.
Open door step. diff.
Set by how much the set point value (Room
temp. day/night) is to increase when the door
is open.
Factory setting:
Set point value difference open door: 3.0 K (0
K – -10 K)
Open door step. diff.
Sensor calibration
Control range limit
> Installer menu > Heating
settings
Over run mode
• Fixed time
> Installer menu > Fan settings >
Door over run
Over run mode
High speed over run
Low speed over run
> Installer menu > Fan
settings > Door over run
Door mode
• Fixed flexible
> Installer menu > Fan settings
Fan settings
Heating settings
Filter guard settings
> Installer menu
Open door step. diff.
•
3.0 K
> Installer menu > Heating
settings
Week program on/off
New program step
Check program
> Installer menu > Week
program
Week program on/off
•
OFF
> Installer menu > Week program
Week program
Fan settings
Heating settings
> Installer menu
Door over run
Door mode
> Installer menu > Fan
settings
Over run mode
•
Auto
> Installer menu > Fan settings >
Door over run
Over run mode
High speed over run
Low speed over run
> Installer menu > Fan
settings > Door over run
Door over run
Door mode
> Installer menu > Fan
settings
Settings fan
Make settings for fan mode.
Door over run
Settings for over run.
In over run mode Auto controls the over run
time depending on how frequently the door is
opened between openings, according to fixed
preset values, according to the table.
Time between
opening [s]
High speed over
run [s]
Low speed over
run [s]
t < 60
30
90
60 < t < 300
10
300
t > 300
0
180
Over run mode Fixed time is selected is one
wants fixed over run times, the times can be
changed during High speed over run and Low
speed over run.
Factory setting:
Over run mode:
Auto (Set time)
High speed over run:
30 s (0 – 180 s)
Low speed over run:
120 s (0 – 300 s)
Door mode
There are three different door modes to
choose from; Auto, Fixed flexible and Fixed
open.
In Fixed flexible mode, the control function
notes whether the door is open or closed.
In Fixed open mode the door is considered
always open and is only controlled based on
the room temperature (see Current stage).
In Auto mode, the control automatically
switches between Flexible and open modes
depending on how often the door has been
open.
Factory setting:
Door mode: Fixed flexible (Fixed open/
Auto)
Settings heating
Make settings for heating-