Frico AGI4500 Original Instructions Manual Download Page 19

AGI4500/6000

22

GB

Replacing the water coil (W) 

1. Shut off the water supply to the unit.
2. Disconnect the connections to the water 

coil.

3. Remove the mounting screws securing the 

coil in the unit and lift the coil out.

4. Install the new coil in reverse order to the 

above.

Draining the water coil (W) 

The drain valve is on the underside of the coil 
on the connector side. 

Trouble shooting  

If the fans are not working or do not blow properly, 
check the following: 

•  Operating power supply to the unit; 

check fuses, circuit-breaker, time switch/
thermostat (if any) that starts and stops the 
unit. 

•  That the air flow selector is correctly set.
•  That the position limit switch is working. 
•  That the overheat protection for the motors 

has not been deployed. 

•  That the intake grille/filter is not dirty. 

If there is no heat, check the following: 

•  Settings for thermostat, omnipolar swtitch 

etc are set so the unit can be expected to 
provide heat. 

 

For units with water coil, also check the following:

•  That the water coil is air free.
•  That there is enough water flow.
•  That incoming water is heated enough.
 
If the fault cannot be rectified, please contact 
a qualified service technician. 

Filter (W)

The distance between the coil plates in 
combination with the hole diameter of 
the intake grille protects against dirt and 
blockage. This normally makes a separate 
filter unnecessary. 
 

Service, repairs and maintenance  

For all service, repair and maintenance 
disconnect the power supply for all 
connections.
  

Maintenance 

 Since fan motors and other components are 
maintenance free, no maintenance other than 
cleaning is necessary. The level of cleaning 
can vary depending on local conditions. 
Undertake cleaning at least twice a year. Inlet 
and exhaust grilles, impeller and elements 
can be vacuum cleaned or wiped using a 
damp cloth. Use a brush when vacuuming 
to prevent damaging sensitive parts. Avoid 
the use of strong alkaline or acidic cleaning 
agents. 
 

Overheating  

All motors are equipped with an integral 
thermal safety cut-out. This will operate, 
stopping the air curtain should the motor 
temperature rise too high. The cut-out 
will automatically reset when the motor 
temperature has returned to within the 
motor’s operating limits.
  

(when the premises are heated and the 
outdoor air is cold).

The air stream should therefore be directed 

outwards to withstand the load. Generally 
speaking, the higher the load, the greater the 
angle that is needed.

  

Basic setting fan speed 

The fan speed when the door is open is set 
using the control. Note that the air flow 
direction and fan speed may need fine 
adjustment depending on the loading of the 
door.
 

Fan replacement 

1. Determine which of the fans is not 

functioning.

2. Disconnect the cables to the relevant fan.
3. Remove the screws securing the fan and lift 

the fan out.

4. Install the new fan as above in reverse 

order.

All manuals and user guides at all-guides.com

Summary of Contents for AGI4500

Page 1: ...AGI4500 6000 Original instructions 18 SE 21 GB 24 NO 27 FR 31 DE 35 ES 39 NL 43 IT 47 PL 51 RU All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 2: ...bersetzung der verwendetenTexte in englischer Sprache siehe die entsprechenden Sprachseiten DE Las p ginas introductorias contienen b sicamente im genes Consulte la traducci n de los textos en ingl s...

Page 3: ...4515 1500 AGI4520 2000 AGI4525 2500 AGI4530 3000 L 300 135 135 255 195 430 80 640 486 185 245 80 10 25 465 1 5 m 4 x M10 2 2 5 3 m 6 x M10 640 430 640 486 25 10 625 50 465 L Vertical mounting Horizont...

Page 4: ...0 4 L mm AGI6012 1200 AGI6018 1800 AGI6024 2400 AGI6030 3000 L 2 25 25 25 25 AGI6012 AGI6018 AGI6024 737 5 25 25 25 25 737 5 737 5 737 5 AGI6030 L 2 25 25 25 25 AGI6012 AGI6018 AGI6024 737 5 25 25 25...

Page 5: ...75 75 575 25 300 300 485 185 730 160 50 75 75 575 25 300 AGI6000 Fig 1c AGI4500 6000 5 L mm AGI6012 1200 AGI6018 1800 AGI6024 2400 AGI6030 3000 2 Inside thread AGI6012 6018 6024 DN25 1 AGI6030 DN32 1...

Page 6: ...me Fig 3 Minimum distance A mm B mm C mm D mm AGI4500 251 625 215 432 AGI6000 296 717 260 524 AGI4500 6000 6 min 300 mm A C D 18 96 5 B 50 13 2X4 All manuals and user guides at all guides com a l l g...

Page 7: ...14 RTRDU7 T10S RTI2 AGB304 MDC MDCDC Controls VRS20 DN20 VRS25 DN25 TVVS20 DN20 TVVS25 DN25 SD20 GP1010 RTI2 T10S AGI W RTRD3 5 2 7 RTRD14 AGB304 MDC RTRDU Level 1 1 2 Level 2 2 SD20 AV20 25 TRVS20 25...

Page 8: ...PE U V TK W TK PE Fan 2 Fan 3 Fan 4 Fan 5 M 3 PE L1 L2 L3 5 6 6 5 6 5 6 5 6 5 AGI 13 14 AGB To terminals L1 L2 and L3 in slave units Bridge RT RT if no door contact is used To terminals 5 6 in slave u...

Page 9: ...W TK PE Fan 2 Fan 3 Fan 4 Fan 5 M 3 PE L1 L2 L3 5 6 6 5 6 5 6 5 6 5 230V A B 2 4 4 t C 6 2 7 T10S 13 14 AGB 1 2 3 KRT1900 To terminals L1 L2 and L3 in slave units Bridge RT RT if no door contact is us...

Page 10: ...TRDU 230V 230V 400V3N Number of fans AGI4515 AGI6012 2 AGI4520 AGI6018 3 AGI4525 AGI6024 4 AGI4530 AGI6030 5 To terminals L1 L2 and L3 in slave units To terminals 5 6 in slave units AGI AGI4500 6000 1...

Page 11: ...AGI4500 6000 230V3 connected only for 230V3 AGI AGI4500 6000 11 Convertible 400V3 230V3 All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 12: ...62 41 0 52 4 5 74 38 0 9 13 Supply water temperature 60 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 60 40 C Room temperature 18 C Type Fan position Airflow m3 h Output kW...

Page 13: ...Max 7300 42 49 5 0 26 1 12 58 41 8 0 72 7 9 AGI4525WH Max 9100 52 46 0 29 1 58 74 42 0 9 10 4 AGI4530WH Max 10900 63 47 0 36 1 85 90 42 5 1 1 16 1 Supply water temperature 80 C Room temperature 18 C O...

Page 14: ...1 26 9 5 Supply water temperature 60 C Room temperature 18 C Outlet air temperature 35 C 1 Water temperature 60 40 C Room temperature 18 C Type Fan position Airflow m3 h Output kW Return water temp C...

Page 15: ...0 39 3 5 70 9 39 6 0 87 16 AGI6024WH Max 12600 72 7 52 0 0 47 3 4 94 39 9 1 15 18 4 AGI6030WH Max 15600 90 9 52 0 0 58 2 1 118 2 40 2 1 45 11 8 Supply water temperature 80 C Room temperature 18 C Outl...

Page 16: ...oil for high water temperature 580 C Horizontal mounting IP54 2 Water heat AGIV4500 WH coil for high water temperature 580 C Vertical mounting IP54 Horizontal mounting Vertical mounting Type Output 5...

Page 17: ...e motor A Length mm Weight kg AGIH6012A 0 6600 85 69 400V3 2 0 1200 51 AGIH6018A 0 9600 87 71 400V3 2 8 1800 75 AGIH6024A 0 12600 88 72 400V3 3 7 2400 97 AGIH6030A 0 15600 89 73 400V3 4 7 3000 120 Typ...

Page 18: ...several units can be mounted next to each other Electrical installation The installation which should be preceded by an omnipolar switch with a contact separation of at least 3 mm should only be wired...

Page 19: ...er unnecessary Service repairs and maintenance For all service repair and maintenance disconnect the power supply for all connections Maintenance Since fan motors and other components are maintenance...

Page 20: ...be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction...

Page 21: ...co AB Tel 46 31 336 86 00 Box 102 SE 433 22 Partille mailbox frico se Sweden www frico se For latest updated information and information about your local contact www frico se All manuals and user guid...

Reviews: