See www.frico.se for additional calculations.
AGI4500/6000
12
Output charts water AGI4500WL
Supply water temperature: 80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 80/60 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max
5500
32
43
0,21
0,8
44
42
0,53
4,8
AGI4520WL Max
7300
42
39
0,25
1,3
61
43
0,75
10,1
AGI4525WL Max
9100
52
37
0,29
2,1
78
43,5
0,96
18
AGI4530WL Max
10900
62
37
0,35
2,1
94
44
1,15
20
Supply water temperature: 70 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 70/50 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max
5500
32
46
0,32
1,8
34
36,5
0,41
3
AGI4520WL Max
7300
42
43
0,378
2,9
48
37,6
0,59
6,5
AGI4525WL Max
9100
52
41
0,436
4,3
62
38
0,75
11,7
AGI4530WL Max
10900
62
41
0,52
4,5
74
38
0,9
13
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 60/40 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max
5500
32
50
0,77
9,7
25
31
0,3
1,7
AGI4520WL Max
7300
42
48
0,85
13,5
35
32
0,43
3,7
AGI4525WL Max
9100
51
45
0,83
14,2
46
33
0,55
6,8
AGI4530WL Max
10900
62
46
1,08
18
55
33
0,66
7,1
Supply water temperature: 55 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
1
Water temperature: 55/35 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
AGI4515WL Max
5500
-
-
-
-
19
28
0,3
1,7
AGI4520WL Max
7300
42
50
2,01
46,7
29
30
0,34
2,5
AGI4525WL Max
9100
-
-
-
-
35
29,5
0,56
7,1
AGI4530WL Max
10900
-
-
-
-
45
30
0,53
4,9
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
– = at the current water temperatures and airflows, the air outlet temperature will be less than 35 °C.
All manuals and user guides at all-guides.com