RWB II ROTARY SCREW COMPRESSOR UNITS
INSTALLATION
S70-200 IOM
Page 15
BATTERY BACKUP
The battery backup is used only for date and time retention
during power interruption. All setpoints and other critical in-
formation are saved on EEPROM chips.
NOTE: It is not necessary to disconnect the battery
backup during extended downtime.
NOTE: The microprocessor will not operate without U24
and U35 EPROM chips installed. When U24 and U35
EPROM chips are not installed, the screen will display:
System Board Initialized
No boot device available,
Press enter to continue.
switch in the starter package as this would bypass the
compressor safety devices.
7. The compressor motor Current Transformer (CT) is installed
on any one phase of the compressor leads.
NOTE: The CT must see all the current of any one phase,
therefore in wye-delta applications BOTH leads of any
one phase must pass through the CT.
CURRENT TRANSFORMER (CT) RATIOS
The CT ratio for various motor sizes (with a 5 amp second-
ary) is given in the following table:
VOLTAGE
HP
200
230
380
460
575
2300
4160
20
100:5
100:5
50:5
50:5
50:5
-
-
25
100:5
100:5
50:5
50:5
50:5
-
-
30
200:5
100:5
100:5
50:5
50:5
-
-
40
200:5
200:5
100:5
100:5
50:5
-
-
50
200:5
200:5
100:5
100:5
100:5
-
-
60
300:5
200:5
200:5
100:5
100:5
-
-
75
300:5
300:5
200:5
200:5
100:5
-
-
100
400:5
300:5
200:5
200:5
200:5
-
-
125
500:5
400:5
300:5
200:5
200:5
-
-
150
600:5
500:5
300:5
300:5
200:5
-
-
200
800:5
600:5
400:5
300:5
300:5
100:5
50:5
250
800:5
800:5
500:5
400:5
300:5
100:5
50:5
300
1000:5 1000:5
600:5
500:5
400:5
100:5
50:5
350
-
1000:5
800:5
500:5
500:5
100:5
100:5
400
-
-
800:5
600:5
500:5
200:5
100:5
450
-
-
1000:5
800:5
600:5
200:5
100:5
500
-
-
1000:5
800:5
600:5
200:5
100:5
600
-
-
1200:5 1000:5
800:5
200:5
100:5
700
-
-
-
1200:5 1000:5
200:5
200:5
800
-
-
-
-
1000:5
300:5
200:5
900
-
-
-
-
1200:5
300:5
200:5
1000
-
-
-
-
-
300:5
200:5
1250
-
-
-
-
-
400:5
200:5
1500
-
-
-
-
-
500:5
300:5
MINIMUM BURDEN RATINGS
The following table gives the minimum CT burden ratings.
This is a function of the distance between the motor starting
package and the compressor unit.
BURDEN
MAXIMUM DISTANCE FROM
RATING
FRICK PANEL
USING #
USING #
USING #
ANSI
VA
14 AWG
12 AWG
10 AWG
B-0.1
2.5
15 ft
25 ft
40 ft
B-0.2
5
35 ft
55 ft
88 ft
B-0.5
12.5
93 ft
148 ft
236 ft
CONTROL POWER REGULATOR
Compressor units that will be used in areas that suffer brown-
outs and other significant power fluctuations can be supplied
with a control power regulator. See the following illustration,
Recommended Regulator Installation.
RECOMMENDED REGULATOR INSTALLATION
REMOVE JUMPERS 6 TO 6B & 2 TO 2B
DC POWER
EMI FILTER
SUPPLY
SEE SOLA CONNECTION CHARTS FOR
INPUT & OUTPUT CONNECTIONS
6
REMOVE FERRITE TUBE
WHEN SOLA IS ADDED,
6B
6
H
NOTE: AT SOLA ASSEMBLY, MAKE WIRES 6, 2, GND, 6B, & 2B,
10 FT LONG. CUT WIRES TO LENGTH AT INSTALLATION
H5
REGULATOR
H3
H4
OUTPUT
INPUT
X1
120/240 V. IN, 120 V. OUT
SOLA #63-23-112-4, 120 VA, 60 HZ
SHOWN HERE- CONSULT FRICK
FOR OTHER VOLTAGES/HZ
SOLA ENCLOSURE
GND TERM
2A
6A
2
3
PS 1
1
LINE
LOAD
GREEN
FERRITE
TUBE
2B
2
GND LUG IN
H2
H1
LUG
X2
GREEN
GND TERM
IN MICRO
2
N
Figure 16