SETPOINT VALUES: (Read/Write)
Frick®
Address
AB
Address
Modbus
Address
Description of Data
Default
Value
Units
Min.
Max.
51460-51489 N70:21460-N70:21489 91461-91490
High Temperature Warning Temp
Mode 3 (Zones 1 - 30)
100
Temp.
-20
150
51490-51519 N70:21490-N70:21519 91491-91520
High Temperature Warning Temp
Mode 4 (Zones 1 - 30)
100
Temp.
-20
150
51550-51579 N70:21550-N70:21579 91551-91579
Low Temperature Warning Temp
Mode 1 (Zones 1 - 30)
100
Temp.
-20
150
51580-51609 N70:21580-N70:21609 91581-91609
Low Temperature Warning Temp
Mode 2 (Zones 1 - 30)
100
Temp.
-20
150
51610-51639 N70:21610-N70:21639 91611-91639
Low Temperature Warning Temp
Mode 3 (Zones 1 - 30)
100
Temp.
-20
150
51640-51669 N70:21640-N70:21669 91641-91670
Low Temperature Warning Temp
Mode 4 (Zones 1 - 30)
100
Temp.
-20
150
51700-51729 N70:21700-N70:21729 91701-91730
New Mode Warning Override
Interval Mode 1 (Zones 1 - 30)
1
Min.
0
250
51730-51759 N70:21730-N70:21759 91731-91760
New Mode Warning Override
Interval Mode 2 (Zones 1 - 30)
1
Min.
0
250
51760-51789 N70:21760-N70:21789 91761-91790
New Mode Warning Override
Interval Mode 3 (Zones 1 - 30)
1
Min.
0
250
51790-51819 N70:21790-N70:21819 91791-91820
New Mode Warning Override
Interval Mode 4 (Zones 1 - 30)
1
Min.
0
250
51850-51879 N70:21850-N70:21879 91851-91879
Variable Fan Max. Speed Heat
Cycle Mode 1 (Zones 1 - 30)
100
Percent
%
0
100
51880-51909 N70:21880-N70:21909 91881-91909
Variable Fan Max. Speed Heat
Cycle Mode 2 (Zones 1 - 30)
100
Percent
%
0
100
51910-51939 N70:21910-N70:21939 91911-91939
Variable Fan Max. Speed Heat
Cycle Mode 3 (Zones 1 - 30)
100
Percent
%
0
100
51940-51969 N70:21940-N70:21969 91941-91970
Variable Fan Max. Speed Heat
Cycle Mode 4 (Zones 1 - 30)
100
Percent
%
0
100
Summary of Contents for QUANTUM LX Control Panel
Page 12: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 12...
Page 34: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 34...
Page 50: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 50...
Page 102: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 102...
Page 110: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 110...