QUANTUM
™
LX EVAPORATOR CONTROL PANEL
COMMUNICATIONS SETUP
090.610-CS (MAY 2016)
Page 39
dress field) is received, each device de-
codes it to find out if it is the addressed
device.
Following the last transmitted character,
a similar interval of at least 3.5 character
times marks the end of the message. A
new message can begin after this inter-
val. The entire message frame must be
transmitted as a continuous stream. If a
silent interval of more than 1.5 character
times occurs before completion of the
frame, the receiving device flushes the
incomplete message and assumes that
the next byte will be the address field of
a new message.
Similarly, if a new message begins ear-
lier than 3.5 character times following a
previous message, the receiving device
will consider it a continuation of the pre-
vious message. This will set an error, as
the value in the final CRC field will not be
valid for the combined messages. A typi-
cal message frame is shown below:
START
ADDRESS FUNCTION
DATA
LRC
CHECK
END
T1-T2-T3-T4
8 Bits
8 Bits
N x 8
Bits
16 Bits
T1-T2-T3-T4
ASCII Query (Read) Example
The examples that follow are based on compres-
sor addresses, but may be modified using the
Evaporator addresses that are shown in the Data
Tables that appear later in this manual. To demon-
strate how an address within the Quantum™ may
be read, the following test can be performed us-
ing Windows HyperTerminal (NOTE: Hyperterminal
cannot be used to test RTU or TCP/IP):
As an example, a MODBUS® command will be
created and sent to obtain the actual Discharge
Pressure value of a compressor. Using the ad-
dress tables found later in this manual, locate the
address for Discharge Pressure. In this case, it is
Frick® Address 2003 (decimal). Since this is the
only address we are interested in obtaining the
value of, send the following message:
: 01 03 07 D3 00 01 21 CRLF
Where:
Message Start:
Quantum™ ID #:
Read Function:
H. O. address (hex):
L. O. address (hex):
H. O. # of Data Registers:
L. O. # of Data Registers:
Error Correction Code:
Carriage Return - Line Feed:
Look at this message on a more basic level, to
understand how the address that we are re-
questing is arrived at. We want to know the ac-
tual value of the Discharge Pressure, Frick® Ad-
dress 2003 (decimal).
The first part of the message will be a Colon
(:). This represents a heads up alert that data is
coming:
: 01 06 1B EE 03 E8 05 CRLF
Where:
Message Start:
Quantum™ ID #:
Write Function:
H. O. address (hex):
L. O. address (hex):
H. O. # of Data Value:
L. O. # of Data Value:
Error Correction Code:
Carriage Return - Line Feed:
}
Any time that a message is sent, all of the Quan-
tum™ panels on the MODBUS® network will
become active, communications-wise, once the
Colon appears. Next, the panels will look at the
first byte following the Colon ( : ). If this byte
equals the Panel ID # of the particular Quantum™
being queried, it will immediately finish reading
the remainder of the message. If the byte does
not equal its ID #, the message will be ignored.
: 01 06 1B EE 03 E8 05 CRLF
Where:
Message Start:
Quantum™ ID #:
Write Function:
H. O. address (hex):
L. O. address (hex):
H. O. # of Data Value:
L. O. # of Data Value:
Error Correction Code:
Carriage Return - Line Feed:
}
00 = H. O. Address
87 = L. O. Address
00 = H. O. # of data registers
01 = L. O. # of data registers
End of
message
CRC Error
Correction
Code
Start of
message
Quantum™
ID
Function
Summary of Contents for QUANTUM LX Control Panel
Page 12: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 12...
Page 34: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 34...
Page 50: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 50...
Page 102: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 102...
Page 110: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 110...