QUANTUM
™
LX EVAPORATOR CONTROL PANEL
COMMUNICATIONS SETUP
090.610-CS (MAY 2016)
Page 53
DIGITAL BOARD VALUES: (Read Only)
Frick®
Address
AB
Address
Modbus
Address
Description of Data
Module
Type
2000
N10:0
42001
Hot Gas (Main)
Out
2001
N10:1
42002
Liquid (Main)
Out
2010
N10:10
42011
Alarm Panel A (Zones 1, 2, 3)
Out
2011
N10:11
42012
Alarm Panel B (Zones 4, 5, 6)
Out
2012
N10:12
42013
Alarm Panel C (Zones 7, 8, 9)
Out
2013
N10:13
42014
Alarm Panel D (Zones 10, 11, 12)
Out
2014
N10:14
42015
Alarm Panel E (Zones 13, 14, 15)
Out
2015
N10:15
42016
Alarm Panel F (Zones 16, 17, 18)
Out
2016
N10:16
42017
Alarm Panel G (Zones 19, 20, 21)
Out
2017
N10:17
42018
Alarm Panel H (Zones 22, 23, 24)
Out
2018
N10:18
42019
Alarm Panel I (Zones 25, 26, 27)
Out
2019
N10:19
42020
Alarm Panel J (Zones 28, 29, 30)
Out
2030
N10:30
42031
Global Ammonia Alarm
Out
2031
N10:31
42032
Global Ammonia Shutdown
Out
2032
N10:32
42033
Global System Alarm
Out
2033
N10:33
42034
Global System Shutdown
Out
2045
N10:45
42046
Panel Heater Status
Out
2100-2129
N10:100-N10:129
42101-42130
Defrost Sensor (Zones 1 -30)
In
2130-2159
N10:130-N10:159
42131-42160
Smoke Detector (Zones 1- 30)
In
2160-2189
N10:160-N10:189
42161-42190
Liquid Valve (Zones 1 – 30)
Out
2190-2219
N10:190-N10:219
42191-42220
Suction Valve (Zones 1 -30)
Out
2220-2249
N10:220-N10:249
42221-42250
Hot Gas Valve (Zones 1 – 30)
Out
2250-2279
N10:250-N10:279
42251-42280
Soft Hot Gas Valve (Zones 1 – 30)
Out
2280-2309
N10:280-N10:309
42281-42310
Bleed Valve (Zones 1 – 30)
Out
2310-2339
N10:310-N10:339
42311-42340
Fan Low (Zones 1 – 30)
Out
2340-2369
N10:340-N10:369
42341-42370
Fan High (Zones 1 – 30)
Out
2370-2399
N10:370-N10:399
42371-42400
Reheat (Zones 1 – 30)
Out
2400-2429
N10:400-N10:429
42401-42430
Auxiliary Digital Output #1 (Zones 1 – 30)
Out
2430-2459
N10:430-N10:459
42431-42460
Auxiliary Digital Output #2 (Zones 1 – 30)
Out
2460-2489
N10:460-N10:489
42461-42490
Auxiliary Digital Output #3 (Zones 1 – 30)
Out
2490-2519
N10:490-N10:519
42491-42520
Auxiliary Digital Output #4 (Zones 1 – 30)
Out
2520-2549
N10:520-N10:549
42521-42550
Auxiliary Digital Output #5 (Zones 1 – 30)
Out
2550-2579
N10:550-N10:579
42551-42580
Auxiliary Digital Output #6 (Zones 1 – 30)
Out
2580-2609
N10:580-N10:609
42581-42610
Auxiliary Digital Output #7 (Zones 1 – 30)
Out
2610-2639
N10:610-N10:639
42611-42640
Auxiliary Digital Output #8 (Zones 1 – 30)
Out
2640-2669
N10:640-N10:669
42641-42670
Auxiliary Digital Output #9 (Zones 1 – 30)
Out
2670-2699
N10:670-N10:699
42671-42700
Auxiliary Digital Output #10 (Zones 1 – 30)
Out
2700-2729
N10:700-N10:729
42701-42730
Auxiliary Digital Input #1 (Zones 1 – 30)
In
2730-2759
N10:730-N10:759
42731-42760
Auxiliary Digital Input #2 (Zones 1 – 30)
In
2760-2789
N10:760-N10:789
42761-42790
Auxiliary Digital Input #3 (Zones 1 – 30)
In
2790-2819
N10:790-N10:819
42791-42820
Auxiliary Digital Input #4 (Zones 1 – 30)
In
2820-2849
N10:820-N10:849
42821-42850
Auxiliary Digital Input #5 (Zones 1 – 30)
In
2850-2879
N10:850-N10:879
42851-42880
Zone Activation (Zones 1 – 30)
In
2880-2909
N10:880-N10:909
42881-42910
Suction Valve (Vent) (Zones 1 30)
Out
2910-2939
N10:910-N10:939
42911-42940
Fan Auxiliary (Zones 1 – 30)
In
2940-2969
N10:940-N10:969
42941-42970
Alarm Zone (Zones 1 – 30)
Out
2970-2999
N10:970-N10:999
42971-43000
Mode Selector 1 (Zones 1 – 30)
In
3000-3029 N10:1000-N10:1029 43001-43030
Mode Selector 2 (Zones 1 – 30)
In
Summary of Contents for QUANTUM LX Control Panel
Page 12: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 12...
Page 34: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 34...
Page 50: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 50...
Page 102: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 102...
Page 110: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 110...