QUANTUM
™
LX EVAPORATOR CONTROL PANEL
COMMUNICATIONS SETUP
090.610-CS (MAY 2016)
Page 82
SETPOINT VALUES: (Read/Write)
Frick®
Address
AB
Address
Modbus
Address
Description of Data
Default
Value
Units
Min.
Max.
39400-39429 N70:9400-N70:9429 79401-79430
Liquid Modulating Valve Integra-
tion Time Mode 3 (Zones 1 – 30)
30
Sec.
0
999
39430-39459
N70:9430-N70:9459
79431-79460
Liquid Modulating Valve Integra-
tion Time Mode 4 (Zones 1 – 30)
30
Sec.
0
999
39490-39519
N70:9490-N70:9519
79491-79520
Suction Modulating Valve Maxi-
mum Open Mode 1 (Zones 1 – 30)
100
Percent
%
0
100
39520-39549
N70:9520-N70:9549
79521-79550
Suction Modulating Valve Maxi-
mum Open Mode 2 (Zones 1 – 30)
100
Percent
%
0
100
39550-39579
N70:9550-N70:9579
79551-79579
Suction Modulating Valve Maxi-
mum Open Mode 3 (Zones 1 – 30)
100
Percent
%
0
100
39580-39609
N70:9580-N70:9609
79581-79609
Suction Modulating Valve Maxi-
mum Open Mode 4 (Zones 1 – 30)
100
Percent
%
0
100
39610-39639
N70:9610-N70:9639
79611-79639
Auxiliary Analog Input # 1 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39640-39669
N70:9640-N70:9669
79641-79670
Auxiliary Analog Input # 2 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39670-39699
N70:9670-N70:9699
79671-79700
Auxiliary Analog Input # 3 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39700-39729
N70:9700-N70:9729
79701-79730
Auxiliary Analog Input # 4 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39730-39759
N70:9730-N70:9759
79731-79760
Auxiliary Analog Input # 5 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39760-39789
N70:9760-N70:9789
79761-79790
Auxiliary Analog Input # 6 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39790-39819
N70:9790-N70:9819
79791-79820
Auxiliary Analog Input # 7 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39820-39849
N70:9820-N70:9849
79821-79850
Auxiliary Analog Input # 8 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39850-39879
N70:9850-N70:9879
79851-79879
Auxiliary Analog Input # 9 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39880-39909 N70:9880-N70:9909
79881-79909
Auxiliary Analog Input # 10 Low
Shutdown Setpoint (Zones 1 – 30)
10
None -10,000 10,000
39910-39939
N70:9910-N70:9939
79911-79939
Hour/Day 1 Mode Schedule 1
(Zones 1 – 30)
0
Integer
0
23
39940-39969
N70:9940-N70:9969
79941-79970
Hour/Day 1 Mode Schedule 2
(Zones 1 – 30)
0
Integer
0
23
39970-39999
N70:9970-N70:9999 79971-80000
Hour/Day 1 Mode Schedule 3
(Zones 1 – 30)
0
Integer
0
23
40000-40029 N70:10000-N70:10029 80001-80030
Hour/Day 1 Mode Schedule 4
(Zones 1 – 30)
0
Integer
0
23
40030-40059 N70:10030-N70:10059 80031-80060
Hour/Day 1 Mode Schedule 5
(Zones 1 – 30)
0
Integer
0
23
40060-40089 N70:10060-N70:10089 80061-80090
Hour/Day 1 Mode Schedule 6
(Zones 1 – 30)
0
Integer
0
23
40090-40119 N70:10090-N70:10119 80091-80120
Hour/Day 1 Mode Schedule 7
(Zones 1 – 30)
0
Integer
0
23
40180-40149 N70:10180-N70:10149 80181-80150
Hour/Day 1 Mode Schedule 8
(Zones 1 – 30)
0
Integer
0
23
Summary of Contents for QUANTUM LX Control Panel
Page 12: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 12...
Page 34: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 34...
Page 50: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 50...
Page 102: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 102...
Page 110: ...QUANTUM LX EVAPORATOR CONTROL PANEL COMMUNICATIONS SETUP 090 610 CS MAY 2016 Page 110...