140.960-IOM (JUN 2016)
Page 11
IDCF & IDC3 EVAPORATIVE CONDENSERS
INSTALLATION
Figure 16 – Fan Cowl Extensions
Detail A
3/8” x 1 1/4” Bolt
3/8” Flatwasher
3/8” Locknut
Motor Removal Davit
IDCF-0709, -0718, and IDC3-7409, -7418 (See Fig. 17)
1. Remove the cover plate from the upper support channel.
2. Rotate the davit assembly to align the bolt head on the
davit with the keyway in the upper support channel and
lower into position. The davit must pass through the
upper and lower support channel and rest on support base.
Cover Plate
(Remove)
Upper Support
Chanel
Lower Support
Chanel
Lower Into
Position
Figure 17 – Motor Removal Davit Installation for
IDCF-0709, -0718, and IDC3-7409, -7418
IDCF/IDC3-1012, 1024, 2012, 1212, 2412, 1224, 2424, 1218,
1236, 2418, AND 2436 AND IDC3-1220
1. Verify the davit support is factory installed next to the access
door. If not installed, remove the bolts next to the access door
(refer to Figure 18b). DO NOT REMOVE TAPPERS. Secure the
davit support by re-installing the bolts.
2. Rotate the davit assembly to align the bolt head on the davit
with the keyway in the upper support channel and lower into
position. The davit must pass through the upper and lower
support channels and rest on the support base.
Figure 18a. Motor Removal Davit Installation
Figure 18b. Davit Support Detail
Bolt, Nut,
and Washer
Tapper
DO NOT
REMOVE
Access Door
CAUTION
Do not remove tappers during installation of motor removal
davit support. Removing tappers will cause the interior
mechanical system to fall.