
HPS Rotary Screw Compressor Units
070.700-IOM (MAR 21)
Page 11
Installation
Economizer (optional)
The economizer option provides an increase in system
capacity and efficiency by subcooling liquid from the
condenser through a heat exchanger or flash tank before
it goes to the evapora tor. The subcooling is provided by
flashing liquid in the economizer cooler to an intermediate
pressure level. The intermediate pressure is provided by a
port located part way down the compres sion process on
the screw compressor.
for the example economizer
systems. Notice a strainer (STR) and a check valve (VCK)
between the economizer vessel and the economizer port
on the compressor in all systems. The strainer prevents
dirt from passing into the compressor and the check valve
prevents oil from flowing from the compressor unit to the
econo mizer vessel during shutdown.
Warning
Other than the isolation valve needed for strainer
cleaning, it is essential that the strainer be the last
device in the economizer line before the compres-
sor. Also, piston-type check valves are necessary for
installation in the economizer line, as opposed to
disc-type check valves. The latter are more prone to
gas-pulsation-induced failure. Place the isolation and
check val ves and strainer as closely as possible to
the compressor, preferably within a few feet.
For refrigeration plants employing multiple compressors on
a common economizing vessel, regardless of economizer
type, each compressor must have a back-pressure regulat-
ing valve in order to balance the economizer load, or gas
flow, between compressors. The problem of balancing load
becomes most important when one or more compressors
run at partial load. In the case of a
flash vessel, there is
no need for the redundancy of a back-pressure regulating
valve on the vessel and each of the multiple compressors.
Omit the
back pressure regulator (BPR) valve on the flash
economizer vessel and use one on each compressor, as
shown in
. It is also best practice to specify the
back-pressure regulating valves, used on economizer lines,
with electric shutoff option. The electric shutoff feature
is necessary to prevent flow from the common econo
-
mizer vessel to the suction side of a stopped compressor,
through the
suction check valve bypass line, if the other
compressors and the common economizer vessel are still
operating and the HV2 valve on the
suction bypass is open.
For refrigeration plants using a Packaged Refrigerant
Recirculation Unit and a direct expansion (DX) economizer
system it is necessary to operate the liquid feed solenoid
on the unit and the liquid feed solenoid on the DX vessel
off of a common signal to avoid liquid overfeed on the DX
economizer system.
If multiple compressors are operated with a common
economizer vessel, it is necessary to install a back-pres-
sure regulator valve with an
electric shutoff option in the
vapor line piped to the compressor's economizer port.
Figure 13: Shell and coil economizer system
HIGH
PRESSURE
LIQUID
INTERMEDIATE PRESSURE
GAS TO COMPRESSOR
SUCTION
STR
VCK
SUBCOOLED
HIGH PRESSURE
LIQUID TO
EVAPORATOR
ECONOMIZER
COOLER
ECON1
HV-2
Figure 14: Direct expansion economizer system
HIGH
PRESSURE
LIQUID
INTERMEDIATE PRESSURE
GAS TO COMPRESSOR
SUCTION
STR
VCK
SUBCOOLED
HIGH PRESSURE
LIQUID TO
EVAPORATOR
ECONOMIZER
COOLER
WIRING
ECON2
HV-2
Figure 15: Flash economizer system
HIGH
PRESSURE
LIQUID
INTERMEDIATE PRESSURE
GAS TO COMPRESSOR
SUCTION
STR
VCK
CONTROLLED
PRESSURE
SATURATED LIQUID
TO EVAPORATOR
ECONOMIZER
VESSEL
BPR
ECON3
HV-2