Frick AGBF Installation Operation & Maintenance Download Page 10

610.020-IOM (NOV 19)

Page 10

EVAPORATOR AND AIR COOLER

INSTALLATION - OPERATION - MAINTENANCE

The heater rods for the drain pan section are attached 
to the underside of the heater sheet which is positioned 
below the coil and held in place with clips. All wiring for 
heater rods is terminated within a junction box located on 
the end tube sheet of the unit.

Wattages for heater elements depend on the room tem-
perature. Check carefully at the time of selection. See 
Table 6

 WARNING

Before performing any service work on the equipment, 
particularly in the vicinity of the fans or any other mov-
ing part, ensure that the correct electrical precautions 
are adhered to. All electrical switchgear for the fans 
must be disconnected, locked out and tagged out.

WATER DEFROST

For water defrost to function correctly it is essential that 
an adequate supply of suitably warm water (> 55°F [13°C]) 
is available at the job site. The defrost method consists 
of the water being evenly distributed over the coil from a 
water distribution pan positioned on top of the coil. Water 
flow is required until all frost has been melted off the 
finned surface.

Control the flow rate by regulating a balancing valve, 
located at the inlet to each unit. See Table 7 for water 

flow pipe sizing. Adjust the flow to ensure full coverage of 
the coil plan area and take care not to allow the water dis-
tribution pan to overflow. Flow rate requirements for each 
unit are indicated on the submittal drawings. During the 
setup and commissioning, the defrost operation must be 
carefully observed to ensure that the entire coil is cleared 
of frost. The time required to clear the coil can vary from 3 
mins to 15 mins. Never exceed 15 mins. If this is the case, 
there may be inadequate water supply or inlet tempera-
ture may be too low.

All water lines within refrigerated spaces must be insu-
lated and heat traced to prevent these lines freezing. Lines 
must also be pitched up to 1/2 in. per linear ft to allow the 
water to drain at the completion of the defrost period.

Large volumes of water also require adequately sized 
condensate drain lines. See Table 8. Condensate drain lines 

must have a minimum inclination of 1/2 in. per linear ft. 
Sufficient fall from the drain pan outlet is required before 
entering the trap. This enables the static head to over-
come the pressure drop of the water flow through the trap. 
Always locate the traps outside the refrigerated space. 
Condensate lines must be heat traced and insulated.

Transportation and rigging

PACKING INFORMATION

All FRICK air coolers are crated so they can be removed 
from a truck with a forklift or a crane. When lifting any 
unit with a forklift it is essential that the forks extend the 
full span of the skid and do not make contact with any 
portion of the unit.
Units are either plastic wrapped with a heavy duty plastic 
wrap and positioned on a skid or have wood crating 
around and on top of the unit, also placed on a skid.
When using a crane to lift the unit, use only the desig-
nated lifting points as detailed on the rigging drawing 
attached to the unit at the time of shipping. Always ensure 
that the lifting points are balanced and evenly spread. 

NOTICE

Never lift unit by placing forks in direct contact with 
the lower portion of the unit or the drain pan.

 

Table 7: 

Pressure and diameter

Pressure 
drop,   
psi/100

Pipe diameter, in.

1

1 1/4

1 1/2

2

2 1/2

3

4

5

2

8

17

23

50

89

144

307

553

5

13

26

38

81

146

236

504

906

10

19

28

56

118

213

344

733

1318

15

24

49

69

147

265

428

912

1640

20

28

56

81

172

309

500

1065

1916

30

35

70

101

214

385

622

1326

2385

40

40

81

117

250

450

727

1549

2786

Table 8: 

Water flow rates for different pipe diameters

Flow rate from 
drain pan (gpm)

15

17

23

50

89

144

307

Pipe diameter 
(in.)

2

26

38

81

146

236

504

Summary of Contents for AGBF

Page 1: ...s may result in personal injury or death damage to the unit or improper operation EVAPORATORS AND AIR COOLERS AGHN AXGHN MANP MXANP MDAN MDXAN AGBF GHN MDN and GGHN Check www FrickCold com for the lat...

Page 2: ...rmation Safety instructions 3 Refrigerant safety 3 General information Warranty statement 3 Product lines 4 Installation Receiving and inspection 5 Air cooler location 5 Air cooler mounting 5 Operatio...

Page 3: ...f approximately 15 to 28 by volume in air When mixed with lubricating oils its flammable concentration range is increased It can explode if re leased in an enclosed space with a source of ignition pre...

Page 4: ...buyer return postage and freight paid This shall constitute full compliance with FRICK s warranty obliga tions hereunder FRICK accepts no liability for the direct or indirect consequences of any modi...

Page 5: ...ce of the air inlet side of the coil from the wall is at least 0 8 x face height to prevent obstructed air flow patterns The face height is the height of the evapo rator coil without the frame Positio...

Page 6: ...pressor overloads Check drain pan for proper drainage Check thermostatic expansion valves for proper super heat settings Adjust all adjustable controls and valves in the field to meet required operati...

Page 7: ...ing dimensions on industry accepted good engineering design principles For direct expansion units select expansion valves in ac cordance with selection data and as required by expansion valve manufact...

Page 8: ...not reverse cycle Incorporate a soft start hot gas solenoid valve in the valve station into evaporators with capacities greater than 15 tons 52 kW This valve allows the coil to ease up to the hot gas...

Page 9: ...4a 115 to 140 8 to 9 5 R507A 115 to 140 8 to 9 5 R134a 50 to 65 3 5 to 4 5 R410a 155 to 185 10 5 to 12 5 NH3 80 to 100 5 5 to 7 Table 5 Hot gas defrost sequence of operation Defrost stages Time in min...

Page 10: ...too low All water lines within refrigerated spaces must be insu lated and heat traced to prevent these lines freezing Lines must also be pitched up to 1 2 in per linear ft to allow the water to drain...

Page 11: ...ree space of at least the length of the unit on the electric connection side to remove the heaters in case of failure 5 Dimensions B and C can be reduced to minimum of 6 in on the refrigerant connecti...

Page 12: ...N GGHN MHF 071 Step 1 When shipped units are stacked but individually skidded Step 2 Separate the top unit from the lower unit Step 3 Remove all crating from the top and sides of the skid Leave the un...

Page 13: ...and Step 1 Units shipped with heavy duty plastic wrap on the skid Step 2 Remove plastic wrap and support members from the unit Step 3 Leave the unit on the skid and place forks under the full span of...

Page 14: ...Step 1 As shipped units are stacked but individually skidded Step 2 Remove all crating from the top and sides of the skids Leave the units on the skids Step 3 Place forks under the full span of the sk...

Page 15: ...nd shipping supports b If unit is foot mounted remove the skid Or If unit is ceiling hung leave the skid in place and secure the hangers to support rods d Remove skid Step 4 a Use a spreader bar when...

Page 16: ...Step 1 Units shipped with heavy duty plastic wrap on the skid Step 2 Remove plastic wrap and support members from the unit Step 3 Leave the unit positioned on the skid Place forks under the full span...

Page 17: ...MBK AGBK MGBK Step 1 Units are shipped stacked but individually skidded Step 2 Remove all crating from the top and sides of skids Leave units on skids Step 3 Place forks under the full span of the sk...

Page 18: ...ans operate silently General state of the unit such as cleanliness and corro sion Cleaning the finned heat exchanger is of particular im portance to ensure smooth operation and long life of the equipm...

Page 19: ...correctly Adjust setting for fan delay duration CLEANING WARNING All power must be disconnected and locked out before any cleaning The drain pan also serves as a cover for hazardous moving parts Oper...

Page 20: ...Defective heater element or elements Replace element or elements Unit incorrectly pitched Check and adjust accordingly Condensate drain line plugged Clean drain line Defective drain line heater Replac...

Page 21: ...610 020 IOM NOV 19 Page 21 EVAPORATOR AND AIR COOLER INSTALLATION OPERATION MAINTENANCE NOTES...

Page 22: ...ynesboro PA 17268 1206 USA Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com FRICK Form 610 020 IOM 2019 11 Supersedes NOTHING Subject to change without notice Published in USA 11 19 PDF 201...

Reviews: