20
WARNING!
Only use fusion units which are authorised by their manufacturer to
process FRIALEN
®
Safety Fittings as part of their function. See DVS
2207-1.
The fusion parameters are contained in the main barcode affixed to the
FRIALEN
®
Safety Fitting
. When using fully automatic fusion units (e.g.
FRIAMAT
®
), the parameters are entered into the fusion unit using the reader.
After reading of the barcode, the fitting data are to be compared with the
data shown on the unit’s display. If they are identical,
start fusion
. Please
observe the operating instruction of the FRIAMAT
®
fusion unit.
The fusion units automatically monitor the fusion process and control the
supplied voltage in determined limits.
The swell indicator only indicates to the performed fusion process. The
proper fusion process is, however, only indicated by the fusion unit!
WARNING!
Keep a distance of one meter to the fusion site during the fusion
process for general safety reasons.
The obtained ACTUAL fusion time is to be compared with the target
fusion time on the unit and to be noted on the pipe or the FRIALEN
®
Safety Fittings.
With this identification it is ensured that no fusion point is overlooked.
After the fusion process has finished always maintain the jointing
pressure for a 10 minute cooling period!
Pipe material
PE 80
PE 100
SDR
17
11
17
11
Maximum permissible working pressure in bar
Gas pipe
2
5
5
10
Water pipe
8
12.5
10
16