![Fresco Pro FFC1A-03H Manual Download Page 31](http://html1.mh-extra.com/html/fresco/pro-ffc1a-03h/pro-ffc1a-03h_manual_2331609031.webp)
FCAC-KTSM-2008-12
Specification
Compact Four-way Cassette Type
29
2. Specification
TYPE
FFC4B-03H
FFC4B-04H
FFC4B-045H
FFC4B-05H
Airflow
CFM
300
400
450
500
m
3
/h
500
630
710
800
Cooling Capacity
W
2989
3780
4982
5480
Btu/h
10200
12900
17000
18700
Heating Capacity
W
4484
5671
7620
8220
Btu/h
15300
19350
26000
28050
Noise
dB(A)
39
41
42
43
Water flow
l/min
8.6
10.8
14.3
15.7
Water resistance
kPa
18.7
14.5
18.3
27.1
Indoor Coil
Number of rows
2
2
3
3
Tube pitch(a)x row pitch(b)
mm
21×13.37
Fin spacing
mm
1.4
Fin type
Hydrophilic aluminium
Tube outside dia. and type
mm
φ7, bare tube
Coil length×height×width
mm
1245.5×210×26.74
1230×210×40.11
Number of circuits
5
5
7
7
Fan motor
Type
Low noise 4-speed fan motor
Number
1
Model
YDK45-4F-3
YDK37-4F-3
Input
W
65/59/55/50
89/83/77/71
89/83/77/71
Capacitor
uF
1uF/450V
1.5uF/450V
2uF/450V
2.5uF/450V
Indoor unit
Dimension (W×H×D)
mm
580×254×580
Packing (W×H×D)
mm
750×340×745
Net/Gross weight
kg
23/29
23/29
Panel
Dimension (W×H×D)
mm
650×20×650
Packing (W×H×D)
mm
715×115×715
Net/Gross weight
kg
3/5
Control mode
wired controller(optional), remote controller (standard)
Auxiliary electrical heater
W
1000
/
Pipe
Water-inlet pipe
RC3/4” internal thread
Water-return pipe
RC3/4” internal thread
Condensate outlet pipe
EVA+LDPE 3/4” external thread
Remark:
1. All performance data above is based upon 0Pa ambient static pressure.
2. Cooling capacity test condition: air inlet Temp. : 27DB
Ԩ
/19WB
Ԩ
, water inlet Temp. 7
Ԩ
, water Temp. difference
5
Ԩ
.
3. Heating capacity test condition:
Air inlet Temp. 21DB
Ԩ
, water inlet Temp. 50 DB
Ԩ
The volume of air and water is same as cooling.
4. Noise level is tested in full-anechoic room.
5. The auxiliary electrical heater is only available for FFC4B-XXXRA series.
Summary of Contents for Pro FFC1A-03H
Page 1: ...FCAC KTSM 2008 12 Content Content i...
Page 21: ......
Page 33: ...FCAC KTSM 2008 12 Service Space Compact Four way Cassette Type 31 4 Service Space...
Page 37: ......
Page 46: ...Service Space FCAC KTSM 2008 12 44 One way Cassette Type 4 Service Space FFC1A 03H FFC1A 04H...
Page 48: ...Wiring Diagrams FCAC KTSM 2008 12 46 One way Cassette Type FFC1A 04H FFC1A 04HA...
Page 51: ......
Page 54: ...Explored View FCAC KTSM 2008 12 52 One way Cassette Type 8 Explored View FFC1A 03H FFC1A 04H...
Page 56: ...Explored View FCAC KTSM 2008 12 54 One way Cassette Type FFC1A 03HA FFC1A 04HA...
Page 70: ...Install the Main Body FCAC KTSM 2008 12 68 The Installation of FFC4A FFC4B...
Page 71: ...FCAC KTSM 2008 12 Install the Main Body The Installation of FFC4A FFC4B 69...
Page 73: ...FCAC KTSM 2008 12 Install the Panel The Installation of FFC4A FFC4B 71...