Specification
FCAC-KTSM-2008-12
10
Four-way Cassette Type
Model No.
FFC4A-950H
FFC4A-1200H
FFC4A-1500H
Airflow (Hi-speed)
CFM
950
1200
1500
m
3
/h
1600
2000
2550
Cooling Capacity (Hi-speed)
W
8220
10390
12866
Btu/h
28050
35450
43900
Heating Capacity (Hi-speed)
W
13845
17585
21043
Btu/h
47240
60000
71800
Noise (Hi-speed)
dB(A)
48
49
49
Water Flow
l/min
23.6
29.8
36.9
Water Pressure Drop
kPa
31.2
44
46
Indoor Coil
Number Of Rows
2
Tube Pitch(A)×Row Pitch(B)
mm
21×13.37
Fin Spacing
mm
1.5
Fin Type
Hydrophilic aluminum
Tube Outside Dia. And Type
mm
φ7
θ
bare tube
Coil dimension (L×H×W)
mm
1959.4×252×26.74
Number Of Circuits
12
Fan Motor
Type
Low noise 4-speed fan motor
Number
1
Model
YDK90-6E
Input
W
165/143/116/100
Capacitor
uF
3uF/450V
3.5uF/450V
3.5uF/450V
Auxiliary Electrical Heater
kW
2.7
Indoor Unit
Dimension (W×H×D)
mm
840×300×840
Packing (W×H×D)
mm
955×317×955
Net/Gross Weight
kg
35/42
Panel
Dimension (W×H×D)
mm
950×46×950
Packing (W×H×D)
mm
1035×90×1035
Net/Gross Weight
kg
6/9
Control Mode
wired controller(optional), remote controller (standard)
Pipe
Water-Inlet Pipe
RC3/4” internal thread
Water-Return Pipe
RC3/4” internal thread
Condensation Water-Outlet Pipe
EVA+L
DPE 3/4” external thread
Remark:
1.
All performance data above is based upon 0Pa ambient static pressure.
2.
Cooling capacity test condition: air inlet Temp. : 27DB
Ԩ
/19WB
Ԩ
, water inlet Temp. 7
Ԩ
, water Temp. difference 5
Ԩ
.
3.
Heating capacity test condition: Air inlet Temp. 20DB
Ԩ
, water inlet Temp. 50 DB
Ԩ
, the volume of air and water is same as
cooling.
4.
Noise level is tested in full-anechoic room.
5.
The auxiliary electrical heater is only available for FFC4A-XXXHA series.
Summary of Contents for Pro FFC1A-03H
Page 1: ...FCAC KTSM 2008 12 Content Content i...
Page 21: ......
Page 33: ...FCAC KTSM 2008 12 Service Space Compact Four way Cassette Type 31 4 Service Space...
Page 37: ......
Page 46: ...Service Space FCAC KTSM 2008 12 44 One way Cassette Type 4 Service Space FFC1A 03H FFC1A 04H...
Page 48: ...Wiring Diagrams FCAC KTSM 2008 12 46 One way Cassette Type FFC1A 04H FFC1A 04HA...
Page 51: ......
Page 54: ...Explored View FCAC KTSM 2008 12 52 One way Cassette Type 8 Explored View FFC1A 03H FFC1A 04H...
Page 56: ...Explored View FCAC KTSM 2008 12 54 One way Cassette Type FFC1A 03HA FFC1A 04HA...
Page 70: ...Install the Main Body FCAC KTSM 2008 12 68 The Installation of FFC4A FFC4B...
Page 71: ...FCAC KTSM 2008 12 Install the Main Body The Installation of FFC4A FFC4B 69...
Page 73: ...FCAC KTSM 2008 12 Install the Panel The Installation of FFC4A FFC4B 71...