![Franklin Electric MonoDrive Owner'S Manual Download Page 20](http://html.mh-extra.com/html/franklin-electric/monodrive/monodrive_owners-manual_2328786020.webp)
INSTALLATION AND SETUP
Electrical Installation
20
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electrical Code and any additional
local codes, or the equivalent. Drive shall be protected by fuse or inverse-time circuit breaker only,
rated 300 V, and a maximum 300% of full load motor output current rating as noted in the table
below.
Fuse/Circuit Breaker and Wire Sizing
1
Based on a 3% voltage drop.
*
90
C Insulation only.
Notes:
•
MonoDrive minimum breaker amps may be lower than AIM Manual specifications because of
the soft-starting characteristic of the drive.
•
SubDrive minimum breaker amps may exceed AIM Manual specifications because the drive is
supplied from single-phase service rather than three-phase.
Risk of damage to VFD
,
or malfunction can occur.
Follow all wire routing and grounding instructions carefully. Inductive currents caused by parallel
wiring, or close proximity between high voltage and control wiring can cause unexpected behav-
iors.
•
Do not run input power and motor wires in the same conduit.
•
Do not run motor wires from multiple VFDs in common conduit.
•
Do not run control wiring parallel with high voltage wiring.
•
Do not install a magnetic contactor or disconnect in the motor circuit.
•
Do not run VFD wiring parallel with house or out-building wiring.
•
Do not use aluminum wires for VFD connections.
•
Do not use with a Ground Fault Circuit Interrupter (GFCI).
•
All wiring must comply with the National Electrical Code and local codes.
•
Improper splicing or damage to motor cable insulation may expose the conductor(s) to
moisture and can produce motor cable failure.
Model
Input
Voltage
Fuse/Breaker
Amps
AWG Copper Wire Sizes, 75° C Insulation, and Panel to Drive Cable Lengths (in feet)
1
14
12
10
8
6
4
3
2
1
1/0
2/0
MonoDrive
208
230
15
15
80
95
125
150
205
250
315
385
500
615
790
970
980
1200
1290
1580
1635
2000
–
–
–
–
MonoDrive XT
208
230
20
20
–
–
85
*
105
140
175
220
265
345
425
550
670
680
835
895
1095
1135
1390
–
–
–
–
SubDrive 15
208
230
15
15
70
*
85
110
135
185
225
280
345
450
550
710
865
880
1075
1160
1415
1465
1795
–
–
–
–
SubDrive 20
208
230
20
20
–
–
–
85
*
115
140
180
220
285
345
450
550
555
680
730
895
925
1130
–
–
–
–
SubDrive 30
208
230
25
25
–
–
–
–
95
*
115
*
145
180
235
285
370
455
460
560
605
740
765
935
–
–
–
–
SubDrive 50
208
230
40
40
–
–
–
–
–
–
–
115
*
150
185
235
290
295
360
385
470
490
600
610
745
735
895
Summary of Contents for MonoDrive
Page 1: ......
Page 56: ...SPECIFICATIONS Notes 56 Notes ...
Page 57: ...SPECIFICATIONS Notes 57 Notes ...
Page 58: ...SPECIFICATIONS Notes 58 Notes ...
Page 61: ...SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R Manuel d utilisation ...
Page 120: ...SPÉCIFICATIONS Normes en vigueur 60 Remarques ...
Page 123: ...SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R Manual del propietario ...