INSTALLATION AND SETUP
Electrical Installation
19
Electrical Installation
Wiring Guidelines
Follow the recommendations in this section to ensure best performance of the SubDrive/Mono-
Drive and to avoid interference with other devices.
Cable Routing
Use the above diagram as a guide when routing wiring to VFD.
1.
Mount the drive as close as possible to the service entrance panel. Wire directly to the service
entrance. Do not connect to a sub-panel.
2. Use a dedicated branch circuit for the drive. Refer to
“Fuse/Circuit Breaker and Wire Sizing” on
3. Route motor wiring out of building as soon as possible. Separate input power and motor wir-
ing by at least 8 in. (20.3 cm). Refer to
“Maximum Motor Cable Length” on page
4. Cross over other branch circuits and facility wiring at a 90
angle. If it is necessary to run wir-
ing in parallel, separate by at least 8 in. (20.3 cm).
All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit routed
individually, not parallel, from high voltage wiring. In addition, any shielded cables should be prop-
erly grounded.
Summary of Contents for MonoDrive
Page 1: ......
Page 56: ...SPECIFICATIONS Notes 56 Notes ...
Page 57: ...SPECIFICATIONS Notes 57 Notes ...
Page 58: ...SPECIFICATIONS Notes 58 Notes ...
Page 61: ...SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R Manuel d utilisation ...
Page 120: ...SPÉCIFICATIONS Normes en vigueur 60 Remarques ...
Page 123: ...SubDrive15 20 30 50 MonoDrive MonoDriveXT Connect NEMA 3R Manual del propietario ...