 INTRODUCTION

The Little Giant simplex control panel is designed specifically for use with the 2-horsepower 
Little Giant Grinder Pump, GP-M231/GP-M201. Complete instructions are provided herein for 
the installation and operation of the residential 230/208 VAC control panel. Properly installed, 
the control panel provides fully automatic or manual control of the grinder pump. The panel 
should be installed by a qualified electrician or technician, with strict adherence to the National 
Electrical Code (NEC), as well as all state or provincial and local codes.
The control panel is equipped with a high water alarm system which activates when the water 
level in the basin or sump rises to a pre-determined level. The alarm system includes a flash-
ing red light mounted on the top of the panel enclosure, as well as an audible alarm buzzer 
which can be silenced with the press of an externally located button. The alarm system will 
automatically re-set when the high level condition is corrected. The control panel is equipped 
with heavy duty electrical components to ensure longevity and reduce the need for repairs 
and maintenance. The enclosure is weatherproof to allow outdoor installation and has a flam-
mability rating which meets UL 94V-0. Figure 1 shows the front of the control panel.
The components inside the control panel include pump circuit breaker, magnetic motor 
contactor, adjustable overload relay, pump hand-off-auto (HOA) switch, alarm silence button, 
pump run indicator light, start and run capacitors, start relay, pump terminal block, float switch 
terminal block, alarm silence relay, control circuit fuse, ground lugs and all necessary wiring 
and brackets. To assist in making proper connections, the pump terminal block is coded and 
labeled (B – black, R – red, W – white) and the float switch terminal block is numbered (see 
Connections). The control panel has the third party safety approvals of UL and cUL.
Read and follow all instructions and safety guidelines thoroughly before installing or operat-
ing the control panel system. Failure to follow the instructions could result in serious bodily 
injury or death and/or property/pump damage.

SAFETY GUIDELINES

WARNING: DISCONNECT ALL POWER BEFORE INSTALLING OR SERVICING THE 
PUMP OR THE CONTROL PANEL!

 1.  Read and follow all safety guidelines and installation/operation instructions. Save 

these instructions for future use and users.

 2.  Follow all national, state or provincial, and local building, plumbing and electrical 

codes and ordinances.

  3.  Do not install or operate the control panel while standing on a wet or damp surface 

or in water.

  4.  Do not smoke, use sparkable electric devices or open flame when installing or operat-

ing the control panel.

  5.  Be sure that the control panel back plate and the power and pump cords are properly 

grounded.

  6.  Never touch any electrical component or wires once power has been supplied to the 

incoming power terminal block.  

  7.  Do not place tools or other objects on the top of the control panel when installing or 

operating the control panel. 

  8.  Do not energize the control panel if an electrical component is damaged or appears dam-

aged. Contact Little Giant technical support.

  9.  Do not energize the control panel if any of the control panel wires are disconnected or 

appear loose, frayed or damaged. Contact Little Giant technical support.

 10.  Extreme care should be taken in the cutting or drilling of of any holes in the control 

panel for wires or cable access. Make sure no control panel components are damaged 

by the saws, drills or other tools.

 11.  Lock the control panel to prevent unauthorized persons or those who may be unfamil-

iar with its operation from opening the control panel. 

 12.  Do not install the control panel in locations classified as hazardous in accordance with 

the most recent National Electrical Code.

 13.  In any installations where property damage and/or personal injury might result from 

inoperative pumps or sump/basin overflow due to power outages, discharge line 

blockage or any other reason, a backup system(s) and/or alarm should be used. 

 14.  Follow all installation/operation instructions and safety guidelines accompanying the 

grinder pumps and/or basin system.

 15.  Make sure no person is touching the pump(s) or near the cutters when testing system 

operation.

LOCATING THE CONTROL PANEL

The control panel should be mounted in a convenient location, preferably close to the pump 
installation. The location should allow clear visibility of the alarm light. Avoid locating the 
control panel in wet locations, such as beneath sweating pipes or faucets, such that the 
user or installer or any necessary tools will not get wet. The surface on which it is mounted 
should not be subject to substantial vibrations. Follow the National Electrical Code and all 
local and state or provincial codes.

MOUNTING THE CONTROL PANEL

The control panel has four corner-located mounting holes. The control panel should be 
securely mounted to a wall or secure vertical structure, using the mounting tabs provided. 
Do not mount in a non-vertical position, as this could affect the start relay operation. Anchors 
should be used with the mounting screws if the vertical structure is masonry or concrete. 
The panel should be mounted approximately 5’ above the floor or ground, as measured to 
the bottom of the panel. Mount the panel such that the door can be easily opened and the 
lockable latches are readily accessible.

POWER REQUIREMENTS

WARNING: DO NOT CONNECT UTILITY SUPPLIED POWER UNTIL ALL CONNECTIONS 
AND CHECKS HAVE BEEN MADE.

The power supply for the control panel must be the proper voltage and within National 
Electric Code (NEC) allowable limits. Simplex grinder pump control panel requires 230 VAC 
or 208 VAC. The power supply conductors should be properly sized for the maximum allow-
able current to the control panel and capable of handling any voltage drops which might 
occur with long service runs. 
The pump power requirements are a single-phase, grounded 230/208 VAC supply. To ensure 
that no other appliances or devices lose power if the pump short circuits, an isolated circuit 
with over-current protection is recommended for the pump power supply.  
The control circuitry requires a single-phase 120 VAC (115 VAC, nominal) supply with a 
neutral wire and a ground wire. The 120 VAC power supply should be from an overcurrent 
protected source and be in accordance with the NEC and all local and state or provincial 
codes. Remove the jumper wire from L1 to 2 if supplying separate 120 VAC power.
Two ground lugs are provided on the control panel back plate for connection of all ground 
wires. The neutral provides the current path for the 120 VAC control and alarm circuitry. 

NEVER

 connect the neutral wire to the back plate ground lugs. 

The control panel does not have access holes or knockouts provided, in order to allow user 
flexibility for determining the power entry. A hole should be cut for the 230 VAC or 208 VAC 
supply and the 120 VAC supply. Weathertight cable clamp connectors should be used at 
the access points and all debris removed from the control panel after cutting.

ELECTRICAL CONNECTIONS

IMPORTANT:

 PRIOR TO MAKING ANY CONNECTIONS, MAKE CERTAIN THAT BOTH 

THE HOA SWITCH AND THE PANEL CIRCUIT BREAKERS ARE SWITCHED TO THE “OFF” 
POSITION. REFERENCE THESE INSTRUCTIONS AND THE ELECTRICAL SCHEMATIC 
SHOWN IN FIGURE 3 & 4 AND INCLUDED WITH THE CONTROL PANEL.
Figure 3 shows the pump power circuitry and the control power circuitry. 

NOTE:

 The over-

load relay current dial is preset at the factory to 14 amps. Little Giant grinder pumps are 
internally protected with a thermal protector integral with the motor, per NEC 430-32(a)2. An 
overload relay is provided in the control panel for extreme case redundant overload protec-
tion and should not be considered the primary overload protection.

NOTE:

  THE SYSTEM DOES NOT INCLUDE CABLES THAT RUN FROM THE JUNCTION 

BOX TO THE CONTROL PANEL. If a junction box is used, these cables must be provided 
by the installer and should be in accordance with the National Electric Code and state or 
provincial and local codes. Connections for the pump power cord and the float switches 
consist of six terminals for the three float switches and four terminals for the pump power 
cable. The float switch terminals are labeled and numbered, while the pump power cable 
uses B for black, R for red and W for white.

1

MGP-1C18-2 

(208/230)

Grinder Pump

Simplex Control Panel

Panneau de commande Simplex 

pour pompe à vilebrequin

Panel de control de la bomba tritu-

radora Simplex 

     

     

E n g i n e e r e d P r o d u c t s

Figure 1.

Franklin Electric Co., Inc.

P. O. Box 12010

Oklahoma City, OK 73157-2010

405.947.2511 • Fax: 405.947.8720

www.LittleGiantPump.com

[email protected]

10.5”

12.5”

9.63”

7.63”

ALARM LIGHT

Figure 2.

Summary of Contents for LittleGIANT MGP-1C18-2

Page 1: ...m operation LOCATING THE CONTROL PANEL The control panel should be mounted in a convenient location preferably close to the pump installation The location should allow clear visibility of the alarm li...

Page 2: ...g could be present caution should be used to ensure the High Leg is not connected to L1 the voltage between L1 and N should be 115 VAC Never connect the neutral N terminal of the incoming power termin...

Page 3: ...endommag Consulter le soutien technique Little Giant 10 Des pr cautions extr mes doivent tre prises durant le per age ou la coupe de trous dans le panneau de commande pour l acc s aux c bles ou aux fi...

Page 4: ...ue la cause d une surcharge soit d termin e et corrig e avant que la pompe soit utilis e de nouveau Apr s la r solution du probl me appuyer bri vement sur le bouton de remise z ro E INTRODUCCION El pa...

Page 5: ...Los cables del interruptor de l mite 1 el Flotador de Apagado LS 1 de flotador de detenci n se etiquetan 9 y 10 los cables del interruptor de l mite 2 de flotador encendido se etiquetan 11 y 12 los c...

Page 6: ...es del foco y aplique una alimentaci n de 120 voltios independiente para determinar si el foco est defectuoso 3 Pump does not operate when HOA switch is in AUTO position La pompe ne fonctionne pas lor...

Page 7: ...mmande d mont e par l utilisateur RETOUR DE PI CES REMPLACER Toute pi ce qui doit tre remplac e conform ment la garantie doit tre retourn e port pay l entreprise Franklin Electric Oklahoma City Oklaho...

Page 8: ...permiten la exclusi n o limitaci n de da os incidentales o emergentes as que la limit aci n o exclusi n arriba indicada puede que no sea aplicable a usted Esta garant a le da a usted derechos legales...

Reviews: