Addressing sensors
Power light
COM1
1. Make sure the sensor is secured on the batteries, and confirm the power light in the lower
left corner is green.
2. Use the TA address modifier (provided) to:
• Connect the connector wire to the TA address modifier and COM1 of the sensor.
• Press the up or down arrow at the bottom of the TA address modifier until the desired
address number appears on the TA address modifier display (1-240).
• Press Enter. The Active light flashes green.
• The address is changed, and the TA address modifier changes to the next address
automatically.
• Connect the TA address modifier to the next sensor, and press Enter until the entire
string is addressed.
IMPORTANT
: Sensors will not address if the cable is connected to COM2. Make sure only the TA
address modifier is connected to the sensor when you attempt to the address the sensor.