The BC can read the monitoring values, one-by-one, from TAs and TCs. This includes:
• Analysis and processing of data received from TAs and TCs.
• A maximum of six battery strings for each BC and 2 strings per COM port.
Specific functions
The BC reads each sensor in series to the end strings or strings including a TC.
• Parameters for string(s) set up in the Integrator software cover upper and lower alarm
limits.
• An automatic alarm function. (When an alarm happens, the E2 light illuminates.)
• The COM port is an RJ-45 (Ethernet) RS-485 Serial.
• Power Options:
• CGBC-300-WD(BC) 85 to 246VAC/110VDC to 370VDC, 10W.
• CGBC-300-WD-48V(BC) 36VDC-72VDC (DC ONLY), 15W.