Commissioning 

 

 

11 

4.4  Assigning a bus address 

Every device connected to the FRAKO Starkstrombus

®

 must have a 

unique  bus  address.  As  factory  default  setting  the  EMG  1500-PN 
has the bus address 1. 

The  software  SYSTEM-SW  can  be  used  to  assign  the EMG 1500-
PN  another  bus  address  in  the  "Bus  coupler  configuration"  dialog 
box. The setting "Max. Number of masters" should not be changed 
and should remain set at 8. 

   Important: 

Each  bus  address  may  only  be  assigned  once  within  a  bus 
system.  For  larger  systems  it  is  recommended  to  draw  up  a 
table of bus addresses. 
 
 

4.5  The Ethernet connection 

At the latest 10 to 15 seconds after switching on the instrument an 
Ethernet  connection  to  the  nearest  hub  or  switch  must  have  been 
established. There is otherwise a risk that the Ethernet driver will not 
be loaded in the EMG 1500-PN. 

Unplugging  or  plugging  in  the  Ethernet  cable  during  operation  has 
no effect. 
 
 

Summary of Contents for EMG 1500-PN

Page 1: ...Gateway EMG 1500 PN EMG 1500 PN Energy Management System Run Made in Germany Gateway Serial Ethernet Connect Bus error Bus Operating manual EMG 1500 PN...

Page 2: ...ollow the operating manual The installation and commissioning may only be carried out by appropriately qualified personnel with due regard for all rules and regulations that are in force The instrumen...

Page 3: ...Connection to the FRAKO Starkstrombus 7 3 2 4 RS 232 connection 8 4 Commissioning 9 4 1 Preparations before commissioning 9 4 2 Instrument self test 9 4 3 Assigning an IP address 9 4 3 1 Assigning the...

Page 4: ...s used to carry out all network settings i e IP address subnet mask and gateway see Section4 3 page 9 The supply voltage must then be removed from the instrument Installation The instrument is mounted...

Page 5: ...SW is used to configure the EMG 1500 PN The EMIS 1500 central unit uses the EMG 1500 PN to access the individual instruments in the Energy Management System and collect their data The Setup programs...

Page 6: ...ards or control cabinets When the instrument is in operation it must not be possible to touch the instrument terminals 3 2 Electrical connections The instrument is connected according to the wiring di...

Page 7: ...shown in Figure 1 on page 6 The two poles of the two wire bus are connected to terminals A and B attention being paid to the correct polarity while the shielding is connected to the terminal The A ter...

Page 8: ...ogether and shielded Types Manufacturer cable type order number cable Twinax 105 Lapp Unitronic Bus CAN 1x2x0 34 2170263 6 8 mm Helukabel CAN BUS 1x2x0 34 801572 6 5 mm Leoni L 02YSCY 1x2x0 34 2 0 120...

Page 9: ...e per second 4 3 Assigning an IP address The EMG 1500 PN requires a unique IP address before it can be accessed via the Ethernet The address is assigned using the software EMG SW supplied as part of t...

Page 10: ...there is at least one data collector of the type EMIS 1500 In addition a connection with this data collector must be in existence An additional bus coupler can be added by clicking the right mouse bu...

Page 11: ...Max Number of masters should not be changed and should remain set at 8 Important Each bus address may only be assigned once within a bus system For larger systems it is recommended to draw up a table...

Page 12: ...established with the EMG 1500 PN The Bus error LED indicates that there are bus related problems in the FRAKO Starkstrombus Each time this LED comes on it indicates that there has been an error in th...

Page 13: ...has not been adopted Switch the device off and then on again After the Ethernet cable has been plugged in the device cannot be accessed During device start up no Ethernet connection could be detected...

Page 14: ...lectrical connection as per EIA RS 485 Transmission rate 76 8 kbit sec Protocol FRAKO Starkstrombus Ethernet interface Plug RJ45 Transmission 10BaseT half duplex Mechanical design Enclosure material P...

Page 15: ...ta 15 EMG 1500 PN Energy Management System Run Made in Germany 140 0 mm 11 4 mm 5 0 mm 59 2 mm Gateway Serial Ethernet Connect Bus error Bus 44 8 mm 35 0 mm 90 0 mm 4 5 mm Figure 3 Enclosure dimension...

Page 16: ...e filters Dynamic compensation of harmonics Reactive power control relays Maximum demand control systems Mains monitoring instruments Cost allocation Energy management systems Sales programme EMG 1500...