EMG 1500 Operating Manual
Commissioning
11
4.4 Assigning a bus address
Every device connected to the FRAKO Starkstrombus
®
must have a
unique bus address. As factory default setting the EMG 1500-PN
has the bus address 1.
The software SYSTEM-SW can be used to assign the EMG 1500-
PN another bus address in the "Bus coupler configuration" dialog
box. The setting "Max. Number of masters" should not be changed
and should remain set at 8.
Important:
Each bus address may only be assigned once within a bus
system. For larger systems it is recommended to draw up a
table of bus addresses.
4.5 The Ethernet connection
At the latest 10 to 15 seconds after switching on the instrument an
Ethernet connection to the nearest hub or switch must have been
established. There is otherwise a risk that the Ethernet driver will not
be loaded in the EMG 1500-PN.
Unplugging or plugging in the Ethernet cable during operation has
no effect.