G3 Cabinets - Service Manual

DDY

Display delay

The display shows the information selected with parameter ‘DDM’ during defrost and for 
‘DDY’ minutes after defrost termination

FID

Evaporator Fans in defrost

YES - Fans active during defrost and drain (‘DRN’) and recovery / NO - Fans off during 
defrost and drain (‘DRN’) and recovery (fan start based on ‘FDD’ or ‘FTO’ - whichever first)

FDD

Evaporator fan re-start 
temperature after defrost

FTO

Maximum evaporator fan stop 
after defrost

FSD

‘Evaporator fan stop delay after 
door opens

Time in seconds: ‘-1’ = fan(s) do not stop / ‘0’ = fan(s) stop instantaneously / ‘1’-’900’ = fans 
stop after prescribed time elapses

FCM

Thermostatic control fan mode ‘NON’ - The fans remain ON all the time (subject to door switch operation and defrosts).

‘TMP’ - Temperature-based control. The fans are ON when the compressor is ON. When 
the compressor is turned OFF, the fans remain ON as long as the temperature difference 
Te-Ta is greater than ‘FDT’

TIM’ - Timed-based control. The fans are ON when the compressor is ON. When the 
compressor is OFF, the fans switch ON and OFF according to parameters ‘FT1’, ‘FT2’ and 
‘FT3’

FDT

Evaporator fan compressor 
stop over-run

Where Evaporator (Te) -Air (Ta) temperature difference for the fans to turn OFF after the 
compressor has stopped

FDH

Temperature differential for fan 
re-start

Example: ‘FDT’ = ‘-1’ and ‘FDH=3’. If compressor is stopped, the fans are OFF when Te> Ta 
‘-1’ (‘FDT’), whereas the fans are ON when Te < Ta ‘-4’ (‘FDT’-’FDH’)

FT1

Fan stop delay after compressor 
stop

FT2 Timed fan stop

When ‘FT2’ = ‘0’ the fans remain on all the time

FT3 Timed fan run

When ‘FT3’ = ‘0’, and ‘FT2’ > ‘0’, the fans remain OFF all the time

ATM

Alarm threshold management

‘NON’ - all temperature alarms are inhibited (the following parameter will be ‘ACC’)

‘ABS’ - the values programmed in ‘ALA’ and ‘AHA’ represent the real alarm thresholds

‘REL’ - the alarm threshold is obtained by the sum of setpoint, thermostat differential and 
‘ALR’ / ‘AHR’

ALA

Low temperature alarm 
threshold

AHA

High temperature alarm 
threshold

ALR

Low temperature alarm 
differential

With ‘ALR’ = ‘0’ the low temperature alarm is excluded

AHR

High temperature alarm 
differential

With ‘AHR’ = ‘0’ the high temperature alarm is excluded

ATI

Probe used for temperature 
alarm detection

PAD

Delay before alarm 
temperature warning at power 
on

ATD

Delay before alarm 
temperature warning

ACC

Condenser periodic cleaning

When the compressor operation time, expressed in weeks, matches the ‘ACC’ value 
programmed, ‘CL’ flashes in the display. With ‘ACC’ = ‘0’ the condenser cleaning warning is 
disabled

ECO

Do not adjust

ESP

Do not adjust

EH0

Do not adjust

EH1

Do not adjust

EPB

Do not adjust

EDM

Do not adjust

EDF

Do not adjust

EDL

Do not adjust

EDO

Do not adjust

EDR

Do not adjust

EFD

Do not adjust

EFT

Do not adjust

EFC

Do not adjust

ESD

Do not adjust

EFS

Do not adjust

EMF

Do not adjust

DSM

Door switch mode

‘NON’ - when ‘DI1’/’T3A’ = ‘DOR’ there is no response to a state change

‘ALR’ - when ‘DI1’/’T3A’ = ‘DOR’ and the digital input is ON, an alarm is generated after 
‘DAD’ minutes

‘STP’ - when  ‘DI1’/’T3A’ = ‘DOR’’ and the digital input is ON, in addition to the alarm, the 
fans are stopped according to FSD and the compressor is stopped after ‘CSD’ seconds

Summary of Contents for ECORPO G3 EP1440G

Page 1: ...Service Manual EP700H EP700M EP700L EP700G EP700F EP700SH EP700SL EP700P EP1440H EP1440M EP1440L EP1440G EP700HH EP700HL EP700LL EP700H2 EP700L2 EP700LL Cabinets...

Page 2: ...your appliance Service Function Parameters Alarm Indicators Probe Data Relay Test Factory Reset Wiring Diagrams Maintenance Welcome to your interactive Foster service manual Here s how it works To re...

Page 3: ...ce should be located on a flat level surface correctly loaded Do not use mechanical devices to accelerate the defrost process Care should be taken not to damage the refrigeration circuit and or system...

Page 4: ...liance produces warm air when operating normally and requires adequate ventilation The dimensions indicated are a minimum As the operating temperature has been pre set no adjustments are required Allo...

Page 5: ...ernal temperature and button 3 Icon Button 1 Compressor running 1 Information menu 2 Keypad locked 2 Increase value 3 Evaporator fans running 3 Standby Exit Confirm 4 Defrost in progress 4 Decrease va...

Page 6: ...nd the shelf above Do not place product on the base of the appliance If it is required to store product on the base of the appliance please contact the Foster parts team to purchase the necessary shel...

Page 7: ...e If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value User Level Parameters Mnemonic Description SP Appliance Set Point Loc Keypad Lock tA Actual air pr...

Page 8: ...DFT accumulated only in run mode FRO Do not use DoD Do not use TAD Do not use DFT Time interval between defrosts When this time has elapsed since the previous defrost in run mode a new defrost cycle i...

Page 9: ...essor stop FT2 Timed fan stop When FT2 0 the fans remain on all the time FT3 Timed fan run When FT3 0 and FT2 0 the fans remain OFF all the time ATM Alarm threshold management NON all temperature alar...

Page 10: ...ler R1 Do not use R1F Do not use R1 Do not use FAN Output enabled for evaporator fan switching FAN Do not use DEF Output enabled for defrost switching DEF Do not use ALO Contacts open when an alarm co...

Page 11: ...ed rate of change toward setpoint actual value away from setpoint mathematical algorithm applied A E the AVG weighted average between TAir T1 and TEvaporator T2 probes T3 TAuxiliary T3 probe value whe...

Page 12: ...60 60 0 0 0 0 0 CT1 4 4 4 4 5 5 4 4 5 4 4 5 5 4 5 4 4 5 CT2 7 6 6 7 5 5 7 6 5 6 7 5 5 6 5 6 6 5 PB 7 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 IT 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1...

Page 13: ...0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ATM REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL ALA 30 30 30 3...

Page 14: ...R DOR DOR NON NON DOR DOR DOR OS3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D3A OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN AHM NON NON NON NON NON NON NON NON NON NON NON NON NO...

Page 15: ...the bottom edge of the front cover If the cover is hinged up or removed for access purposes the door switch will not function and the door open alarm will be displayed tA Air probe has failed Call you...

Page 16: ...522 113 347 117 294 25 84 823 87 559 90 374 20 66 27 68 237 70 255 15 52 229 53 65 55 104 10 41 477 42 506 43 557 5 33 147 33 892 34 651 0 26 678 27 219 27 767 5 21 63 22 021 22 417 10 17 643 17 926...

Page 17: ...ve at all other times subject to the parameter FCM Door Switch The appliance is fitted with a magnetic door switch located in the underside of the front cover Where the door switch is open and followi...

Page 18: ...parameter DTO or the temperature set in parameter DLI is reached Where parameter TE is set to NO defrost will function on a time basis only Upon completion of the defrost cycle the appliance will resu...

Page 19: ...skets Door gaskets should be inspected periodically and cleaned where necessary with a warm damp cloth Do not use aggressive cleaning materials on the door gaskets Where door gaskets are damaged or no...

Page 20: ...20 www fosterrefrigerator com Wiring Diagrams EP700H Integral Condensing Unit...

Page 21: ...21 G3 Cabinets Service Manual EP700H Remote Condensing Unit...

Page 22: ...22 www fosterrefrigerator com EP700G Integral Condensing Unit...

Page 23: ...23 G3 Cabinets Service Manual EP700G Remote Condensing Unit...

Page 24: ...24 www fosterrefrigerator com EP700P Integral Condensing Unit...

Page 25: ...25 G3 Cabinets Service Manual EP700P Glass Door Integral Condensing Unit...

Page 26: ...26 www fosterrefrigerator com EP700F Integral Condensing Unit...

Page 27: ...27 G3 Cabinets Service Manual EP700F Remote Condensing Unit...

Page 28: ...28 www fosterrefrigerator com EP700M EP700L Integral Condensing Unit...

Page 29: ...29 G3 Cabinets Service Manual EP700M EP700L Remote Condensing Unit...

Page 30: ...30 www fosterrefrigerator com EP700HH Integral Condensing Unit...

Page 31: ...31 G3 Cabinets Service Manual EP700HH Remote Condensing Unit...

Page 32: ...32 www fosterrefrigerator com EP700HL Integral Condensing Unit...

Page 33: ...33 G3 Cabinets Service Manual EP700HL Remote Condensing Unit...

Page 34: ...34 www fosterrefrigerator com EP700LL Integral Condensing Unit...

Page 35: ...35 G3 Cabinets Service Manual EP700LL Remote Condensing Unit...

Page 36: ...36 www fosterrefrigerator com EP820HU Integral Condensing Unit...

Page 37: ...37 G3 Cabinets Service Manual EP1440H Integral Condensing Unit...

Page 38: ...38 www fosterrefrigerator com EP1440H Remote Condensing Unit...

Page 39: ...39 G3 Cabinets Service Manual EP1440G Integral Condensing Unit...

Page 40: ...40 www fosterrefrigerator com EP1440G Remote Condensing Unit...

Page 41: ...41 G3 Cabinets Service Manual EP1440M EP1440L Integral Condensing Unit...

Page 42: ...42 www fosterrefrigerator com EP1440M EP1440L Remote Condensing Unit...

Page 43: ...43 G3 Cabinets Service Manual...

Page 44: ...sterrefrigerator com Document ID code 00 570505 v1 By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn For service and spares For ser...

Reviews: