G3 Cabinets - Service Manual
DDY
Display delay
The display shows the information selected with parameter ‘DDM’ during defrost and for
‘DDY’ minutes after defrost termination
FID
Evaporator Fans in defrost
YES - Fans active during defrost and drain (‘DRN’) and recovery / NO - Fans off during
defrost and drain (‘DRN’) and recovery (fan start based on ‘FDD’ or ‘FTO’ - whichever first)
FDD
Evaporator fan re-start
temperature after defrost
FTO
Maximum evaporator fan stop
after defrost
FSD
‘Evaporator fan stop delay after
door opens
Time in seconds: ‘-1’ = fan(s) do not stop / ‘0’ = fan(s) stop instantaneously / ‘1’-’900’ = fans
stop after prescribed time elapses
FCM
Thermostatic control fan mode ‘NON’ - The fans remain ON all the time (subject to door switch operation and defrosts).
‘TMP’ - Temperature-based control. The fans are ON when the compressor is ON. When
the compressor is turned OFF, the fans remain ON as long as the temperature difference
Te-Ta is greater than ‘FDT’
TIM’ - Timed-based control. The fans are ON when the compressor is ON. When the
compressor is OFF, the fans switch ON and OFF according to parameters ‘FT1’, ‘FT2’ and
‘FT3’
FDT
Evaporator fan compressor
stop over-run
Where Evaporator (Te) -Air (Ta) temperature difference for the fans to turn OFF after the
compressor has stopped
FDH
Temperature differential for fan
re-start
Example: ‘FDT’ = ‘-1’ and ‘FDH=3’. If compressor is stopped, the fans are OFF when Te> Ta
‘-1’ (‘FDT’), whereas the fans are ON when Te < Ta ‘-4’ (‘FDT’-’FDH’)
FT1
Fan stop delay after compressor
stop
FT2 Timed fan stop
When ‘FT2’ = ‘0’ the fans remain on all the time
FT3 Timed fan run
When ‘FT3’ = ‘0’, and ‘FT2’ > ‘0’, the fans remain OFF all the time
ATM
Alarm threshold management
‘NON’ - all temperature alarms are inhibited (the following parameter will be ‘ACC’)
‘ABS’ - the values programmed in ‘ALA’ and ‘AHA’ represent the real alarm thresholds
‘REL’ - the alarm threshold is obtained by the sum of setpoint, thermostat differential and
‘ALR’ / ‘AHR’
ALA
Low temperature alarm
threshold
AHA
High temperature alarm
threshold
ALR
Low temperature alarm
differential
With ‘ALR’ = ‘0’ the low temperature alarm is excluded
AHR
High temperature alarm
differential
With ‘AHR’ = ‘0’ the high temperature alarm is excluded
ATI
Probe used for temperature
alarm detection
PAD
Delay before alarm
temperature warning at power
on
ATD
Delay before alarm
temperature warning
ACC
Condenser periodic cleaning
When the compressor operation time, expressed in weeks, matches the ‘ACC’ value
programmed, ‘CL’ flashes in the display. With ‘ACC’ = ‘0’ the condenser cleaning warning is
disabled
ECO
Do not adjust
ESP
Do not adjust
EH0
Do not adjust
EH1
Do not adjust
EPB
Do not adjust
EDM
Do not adjust
EDF
Do not adjust
EDL
Do not adjust
EDO
Do not adjust
EDR
Do not adjust
EFD
Do not adjust
EFT
Do not adjust
EFC
Do not adjust
ESD
Do not adjust
EFS
Do not adjust
EMF
Do not adjust
DSM
Door switch mode
‘NON’ - when ‘DI1’/’T3A’ = ‘DOR’ there is no response to a state change
‘ALR’ - when ‘DI1’/’T3A’ = ‘DOR’ and the digital input is ON, an alarm is generated after
‘DAD’ minutes
‘STP’ - when ‘DI1’/’T3A’ = ‘DOR’’ and the digital input is ON, in addition to the alarm, the
fans are stopped according to FSD and the compressor is stopped after ‘CSD’ seconds
Summary of Contents for ECORPO G3 EP1440G
Page 20: ...20 www fosterrefrigerator com Wiring Diagrams EP700H Integral Condensing Unit...
Page 21: ...21 G3 Cabinets Service Manual EP700H Remote Condensing Unit...
Page 22: ...22 www fosterrefrigerator com EP700G Integral Condensing Unit...
Page 23: ...23 G3 Cabinets Service Manual EP700G Remote Condensing Unit...
Page 24: ...24 www fosterrefrigerator com EP700P Integral Condensing Unit...
Page 25: ...25 G3 Cabinets Service Manual EP700P Glass Door Integral Condensing Unit...
Page 26: ...26 www fosterrefrigerator com EP700F Integral Condensing Unit...
Page 27: ...27 G3 Cabinets Service Manual EP700F Remote Condensing Unit...
Page 28: ...28 www fosterrefrigerator com EP700M EP700L Integral Condensing Unit...
Page 29: ...29 G3 Cabinets Service Manual EP700M EP700L Remote Condensing Unit...
Page 30: ...30 www fosterrefrigerator com EP700HH Integral Condensing Unit...
Page 31: ...31 G3 Cabinets Service Manual EP700HH Remote Condensing Unit...
Page 32: ...32 www fosterrefrigerator com EP700HL Integral Condensing Unit...
Page 33: ...33 G3 Cabinets Service Manual EP700HL Remote Condensing Unit...
Page 34: ...34 www fosterrefrigerator com EP700LL Integral Condensing Unit...
Page 35: ...35 G3 Cabinets Service Manual EP700LL Remote Condensing Unit...
Page 36: ...36 www fosterrefrigerator com EP820HU Integral Condensing Unit...
Page 37: ...37 G3 Cabinets Service Manual EP1440H Integral Condensing Unit...
Page 38: ...38 www fosterrefrigerator com EP1440H Remote Condensing Unit...
Page 39: ...39 G3 Cabinets Service Manual EP1440G Integral Condensing Unit...
Page 40: ...40 www fosterrefrigerator com EP1440G Remote Condensing Unit...
Page 41: ...41 G3 Cabinets Service Manual EP1440M EP1440L Integral Condensing Unit...
Page 42: ...42 www fosterrefrigerator com EP1440M EP1440L Remote Condensing Unit...
Page 43: ...43 G3 Cabinets Service Manual...